6) Troubleshooting at breaker tripping
Check items
1
Check the breaker capacity.
2
Check the a short circuit or grounding in the electrical
system other than the inverter.
3
Check the resistance between terminals on the terminal
block TB1 for power source.
1
0 ~ several ohms or improper megohm value
4
Checking by powering again.
1
Main power source circuit breaker tripping
2
No display of remote controller
5
Operational check by operating air conditioner
1
Normal operation without breaker tripping.
2
Breaker tripping
Measures to be taken
The breaker’s capacity should be proper.
Correct any defects.
Check each part inside power circuit (resistance,
megohm or the like).
a) Diode stack
Refer to “Troubleshooting of diode stack.”
b) Power transistor
Refer to “Troubleshooting of power transistor.”
c) Rush current protection resistor
d) Electromagnetic contactor
e) DC reactor
f ) SCRM
*
Refer to “Individual Parts Failure Judgement
Methods.”
*
For the constant capacity unit, check d) , f) only.
a) As there is a possibility of instantaneous short
circuit generated, find the mark of the short circuit
for repair.
b) When a) is not applicable, the compressor may be
faulty.
The ground fault of inverter output/compressor can be
supposed.
Disconnect the wiring to the compressor and check the
insulation resistance of the following parts with a
megger.
a) Compressor terminals.
b) Inverter output.