–138–
Thyristor module
(SCRM)
<Judgment Method>
Measure the resistance between each of the SCRM pins and judge if there is a failure or not by
the resulting values.
<Judgment Values 1>
Check between G and K.
Use the smallest resistance range on the tester.
Judgment Value: 1.5
Ω
~ 80
Ω
<Judgment Values 2>
Check between AK1 and AK2.
Use the greatest resistance range on the tester.
Judgment Value: 60 k
Ω
~
∞ Ω
<External View>
<Internal Circuit Diagrams>
K
AK1
AK2
G
G
K
K
AK1
AK2
G
G
K
K
AK1
AK2
G
G
K
AK1
AK1
AK1
AK2
AK2
AK2
K
G
K
G
K
G
G
K
G
K
G
K
Summary of Contents for CITY MULTI PUHY-400YMF-B
Page 16: ... 13 FANCON board CNV CNW CNU CNFC2 ...
Page 17: ... 14 RELAY board CN51C2 CNOUT2 CNRT2 CN52F CN52C2 CNCH ...
Page 26: ... 23 ...
Page 50: ... 47 ...
Page 152: ... 149 Model PUHY 400YMF B 500YMF B ...