<Največje dolžine>
1
ME Daljinski upravljalnik [Fig. 11.3.1] [Fig. 11.3.4] (Str. 15, 16)
• Maksimalna dolžina prek toplotnih virov: L
1
+L
2
+L
3
+L
4
in L
1
+L
2
+L
3
+L
5
in L
1
+L
2
+L
6
≤ 500 m [1.640 ft] (1,25 mm
2
[AWG 16] ali več)
• Maksimalna dolžina prenosnega voda: L
1
in L
3
+L
4
in L
3
+L
5
in L
6
in L
2
+L
6
≤ 200 m [656 ft] (1,25 mm
2
[AWG 16] ali več)
• Dolžina kabla daljinskega upravljalnika:
1
,
2
,
3
,
4
≤ 10 m [32 ft] (0,3 do 1,25 mm
2
[AWG 22 do 16])
Če dolžina presega 10 m [32 ft], uporabite oklopljen kabel 1,25 mm
2
[AWG 16]. Dolžina tega odseka (L
8
) mora biti vključena
pri izračunu maksimalne dolžine in celotne dolžine.
2
MA Daljinski upravljalnik [Fig. 11.3.2] [Fig. 11.3.5] (Str. 15, 17)
• Maksimalna dolžina prek toplotnih vira (kabel ME): L
1
+L
2
+L
3
+L
4
in L
1
+L
2
+L
6
≤ 500 m [1.640 ft] (1,25 mm
2
[AWG 16] ali več)
• Maksimalna dolžina prenosnega voda (kabel ME): L
1
in L
3
+L
4
in L
6
in L
2
+L
6
≤ 200 m [656 ft] (1,25 mm
2
[AWG 16] ali več)
• Dolžina kabla daljinskega upravljalnika:
m
1
+
m
2
in
m
1
+
m
2
+
m
3
+
m
4
≤ 200 m [656 ft] (0,3 do 1,25 mm
2
[AWG 22 do 16])
3
Ojačevalnik prenosa [Fig. 11.3.3] [Fig. 11.3.6] (Str.16, 17)
• Maksimalna dolžina prenosnega voda (kabel ME): Za PQHY
1
L
11
+ L
12
+ L
13
+ L
15
+ L
16
≤ 200 m [656 ft] (1,25 mm
2
[AWG 16])
2
L
11
+ L
12
+ L
13
+ L
15
+ L
17
≤ 200 m [656 ft] (1,25 mm
2
[AWG 16])
3
L
11
+ L
12
+ L
14
≤ 200 m [656 ft] (1,25 mm
2
[AWG 16])
4
L
16
+ L
15
+ L
13
+ L
14
, L
14
+ L
13
+ L
15
+ L
17
≤ 200 m [656 ft] (1,25 mm
2
[AWG 16])
Za PQRY
1
L
11
+ L
12
+ L
13
+ L
14
+ L
16
+ L
17
≤ 200 m [656 ft] (1,25 mm
2
[AWG 16])
2
L
11
+ L
12
+ L
13
+ L
14
+ L
16
+ L
18
≤ 200 m [656 ft] (1,25 mm
2
[AWG 16])
3
L
11
+ L
12
+ L
13
+ L
15
≤ 200 m [656 ft] (1,25 mm
2
[AWG 16])
4
L
17
+ L
16
+ L
14
+ L
15
, L
15
+ L
14
+ L
16
+ L
18
≤ 200 m [656 ft] (1,25 mm
2
[AWG 16])
• Dolžina kabla daljinskega upravljalnika:
1
,
2
≤ 10 m [32 ft] (0,3 do 1,25 mm
2
[AWG 22 do 16])
Če dolžina presega 10 m [32 ft], uporabite oklopljen kabel 1,25 mm
2
[AWG 16] in dolžino tega odseka (L
15
in L
18
) vključite pri
izračunu skupne dolžine in največje dolžine za daljinski upravljalnik.
11.4. Napeljava glavnega električnega napajanja in kapaciteta opreme
Shematski diagram napeljave (primer)
[Fig. 11.4.1] (Str. 17)
A
Stikalo (odklopnik za zaščito pred nadtokom in odklopnik uhajavega toka)
B
Odklopnik uhajavega toka
C
Toplotni vir
D
Ohišje za vlečenje kablov
E
Notranja naprava
F
Upravljalnik BC (standarden ali glavni) (za PQRY-P·Y(S)LM-A)
F
'
Upravljalnik BC (podrejeni) (za PQRY-P·Y(S)LM-A)
Debelina voda za glavno električno napajanje, kapacitete stikal in sistemska impedanca
Model
Najmanjša
velikost (mm
2
[AWG])
Odklopnik uhajavega toka
Lokalno stikalo (A)
Odklopnik za
zaščito pred
nadtokom (NFB) (A)
Napajalni
kabel
Napajalni kabel za
točko vejitve cevi
Ozemljitvena
žica
Kapaciteta
Varovalka
WY
PQHY-P200YLM-A
4,0 [12]
-
4,0 [12]
30 A 100 mA 0,1 s ali manj
25
25
30
PQHY-P250YLM-A
4,0 [12]
-
4,0 [12]
30 A 100 mA 0,1 s ali manj
25
25
30
PQHY-P300YLM-A
4,0 [12]
-
4,0 [12]
30 A 100 mA 0,1 s ali manj
25
25
30
PQHY-P350YLM-A
4,0 [12]
-
4,0 [12]
30 A 100 mA 0,1 s ali manj
25
25
30
PQHY-P400YLM-A
4,0 [12]
-
4,0 [12]
30 A 100 mA 0,1 s ali manj
32
32
30
PQHY-P450YLM-A
6,0 [10]
-
6,0 [10]
40 A 100 mA 0,1 s ali manj
40
40
40
PQHY-P500YLM-A
6,0 [10]
-
6,0 [10]
40 A 100 mA 0,1 s ali manj
40
40
40
PQHY-P550YLM-A
10,0 [8]
-
10,0 [8]
60 A 100 mA 0,1 s ali manj
63
63
60
PQHY-P600YLM-A
10,0 [8]
-
10,0 [8]
60 A 100 mA 0,1 s ali manj
63
63
60
WR2
PQRY-P200YLM-A
4,0 [12]
-
4,0 [12]
30 A 100 mA 0,1 s ali manj
25
25
30
PQRY-P250YLM-A
4,0 [12]
-
4,0 [12]
30 A 100 mA 0,1 s ali manj
25
25
30
PQRY-P300YLM-A
4,0 [12]
-
4,0 [12]
30 A 100 mA 0,1 s ali manj
25
25
30
PQRY-P350YLM-A
4,0 [12]
-
4,0 [12]
30 A 100 mA 0,1 s ali manj
25
25
30
PQRY-P400YLM-A
4,0 [12]
-
4,0 [12]
30 A 100 mA 0,1 s ali manj
32
32
30
PQRY-P450YLM-A
6,0 [10]
-
6,0 [10]
40 A 100 mA 0,1 s ali manj
40
40
40
PQRY-P500YLM-A
6,0 [10]
-
6,0 [10]
40 A 100 mA 0,1 s ali manj
40
40
40
PQRY-P550YLM-A
10,0 [8]
-
10,0 [8]
60 A 100 mA 0,1 s ali manj
63
63
60
PQRY-P600YLM-A
10,0 [8]
-
10,0 [8]
60 A 100 mA 0,1 s ali manj
63
63
60
1. Za toplotne vire in notranje naprave uporabljajte namenske električne napajalnike. Zagotovite, da bo napeljava za OC in OS izvedena ločeno.
2. Pri izvedbi električne napeljave in povezav upoštevajte razmere v okolju (temperaturo okolja, neposredno sončno svetlobo, dež itd.).
3. Velikost vodov predstavlja minimalno velikost kovinskih cevi za vode. Če napetost pada, uporabite vod z eno stopnjo večjim premerom.
Poskrbite, da napetost napajalnika ne pade za več kot 10%.
4. Način izvedbe napeljave mora biti v skladu s predpisi CSA22-1 in ANSI/NFPA No.70 v zvezi z električno napeljavo.
5. Električni napajalni vodi delov aparatov za uporabo na prostem ne smejo biti lažji od polikloroprenskih oplaščenih gibkih vodov (tip 245 IEC57).
6. Monter klimatske naprave dobavi stikalo z vsaj 3 mm [1/8 in] kontaktne razdalje na vsakem polu.
7. Če je napajalni kabel poškodovan, ga mora zamenjati proizvajalec, serviser ali druga usposobljena oseba, da ne pride do nevarnosti.
Opozorilo:
• Poskrbite, da bodo za priklop uporabljeni predpisani vodi in zagotovite, da priključne sponke ne bodo izpostavljene zunanji sili. Če priključki niso čvrsto
pritrjeni, lahko pride so segrevanja ali požara.
• Poskrbite, da bo uporabljen ustrezen tip stikala za zaščito pred nadtokom. Nastali nadtok lahko vsebuje tudi nekaj enosmernega toka.
Pazljivo:
• Na nekaterih mestih montaže bo potrebna namestitev odklopnika za uhajavi tok za frekvenčni menjalnik. Če odklopnik za uhajavi tok ni nameščen,
obstaja nevarnost električnega udara.
• Ne uporabljajte drugih elementov razen izklopnika in varovalke z ustrezno kapaciteto. Če uporabite varovalno ali vodnik s preveliko kapaciteto, lahko
pride do napake v delovanju ali požara.