20
Control Mode
Control Details
Remarks
2-2. Residual heat exclusion mode
When the condition changes the auxiliary heater ON to OFF (thermostat or operation
stop, etc), the indoor fan operates in [Low] mode for 1 minute.
This control operates
the same for the model
without auxiliary heater.
2-3. Thermo-OFF mode
When the temperature adjustment function changes to OFF, the indoor fan operates in
[Extra low].
2-4. Heat defrosting mode
The indoor fan stops.
3. Vane control
(Up/down vane
change)
,QLWLDOVHWWLQJ2))ĺ+($7āāā>ODVWVHWWLQJ@
When changing the mode from exception of HEAT to HEAT operation
···[Downward C]
(2) Vane position:
+RUL]RQWDOĺ'RZQZDUG$ĺ'RZQZDUG%ĺ'RZQZDUG&
(3) Restriction of vane position
1
7KHYDQHLVKRUL]RQWDOO\¿[HGIRUWKHIROORZLQJPRGHV
(The control by the remote controller is temporally invalidated and control by the unit.)
7KHUPR2))
+RWDGMXVW>([WUDORZ@PRGH
+HDWGHIURVWPRGH
OCH516B