8-2. Function of DIP switch
PKFY-P06NBMU-E2 PKFY-P06NBMU-E2R1
7KHEODFNVTXDUHŶLQGLFDWHVDVZLWFKSRVLWLRQ
Switch
Pole
Function
Operation by switch
Effective
timing
Remarks
ON
OFF
SW1
Mode
Selection
1
Thermistor
<Room temperature
detection> position
Built-in remote
controller
Indoor unit
Under
suspension
Address board
ON
OFF
ON
OFF
1 2 3 4 5 6 7 8 9 10
<Initial setting>
*
1
Refer to <Table A> below.
*
2
The model is not capable of fresh air intake.
*
3
SW1-5 has different function for the listed models.
The standard function of SW1-5 for the
listed models are different from that for
other models.
When SW1-5 is OFF, even with the free
contact function of TG-2000, the external
heater signal function of the remote
display cannot be changed.
When the free contact function of TG-2000
is used, set SW1-5 to ON together with
SW1-9 and SW1-10.
2
Filter clogging
detection
Provided
Not provided
3
Filter cleaning sign
2,500 hr
100 hr
4
Fresh air intake*
2
Not effective
Not effective
5
Remote indication
(CN52-2 output signal)
Thermo-ON signal
indication
External heater
signal*
3
6
+XPLGL¿HUFRQWURO
Fan operation Heating
mode
Thermo-ON operation at
heating mode
7
$LUÀRZVHWLQFDVHRI
heat thermo-OFF
Low*
1
Extra low*
1
8
6HWWLQJDLUÀRZ
1
Depends on SW1-7
9
Auto restart function
Effective
Not effective
10
Power ON/OFF by breaker Effective
Not effective
SW2
Capacity
code
setting
1–4
Model
SW2
ON
OFF
1 2 3 4
P06
Before
power
supply
ON
Indoor controller board
SW3
Function
Selection
1
Heat pump/Cool only
Cooling only
Heat pump
Under
suspension
Indoor controller board
<Initial setting>
ON
OFF
1 2 3 4 5 6 7 8 9 10
*
4
At cooling mode, each angle can be
used only 1 hour.
*
5
Please do not use SW3-9,10 as
trouble might be caused by the
usage condition.
*
6
6HFRQGVHWWLQJLVWKHVDPHDV¿UVW
setting.
2
Louver
—
—
3
Vane
Available Not
available
4
Vane swing
—
—
5
Vane horizontal angle
Second setting*
6
First setting
6
Vane cooling limit angle
setting*
4
Horizontal angle
Down B, C
7
Changing the opening of
linear expansion valve
Effective
Not effective
8
Heating 4 degree (7.2
_
F) up Not
effective
Effective
9
Target superheat setting*
5
—
—
10
Target superheat setting*
5
—
—
<Table A>
SW1-7
SW1-8
OFF
OFF
Extra low
ON
OFF
Low
OFF
ON
6HWWLQJDLUÀRZ
ON
ON
stop
Continue to the next page