Adjustment of super heat of heat
exchanger outlet port of indoor unit
during cooling.
2
Adjustment of sub-cool of heat ex-
changer outlet port of indoor unit
during heating.
Indoor unit control (Thermostat).
1
Indoor unit control (Freeze preven-
tion, hot adjust, etc.).
2
LEV control during heating (sub-cool
detection).
LEV control during cooling (super-heat
detection).
Uses the operating pressure to adjust
the operating frequency and adjust the
amount of circulating refrigerant.
When there is a load that cannot be
adjusted by MC1, this function ensures
the stable flow of refrigerant.
[4] List of Major Component Functions
Name
Code
(Function)
Electronic
expansion
valve
Thermistor
Compres-
sor
Outdoor unit
Inspection method
DC 12 V
Amount of opening of the
stepping motor drive valve
60 to 2000 pulse.
(Gear Type)
R
0
= 15 k
Ω
B
0/80
= 3460
Rt =
15exp{3460( - )}
0
°
C: 15 k
Ω
10
°
C: 9.7 k
Ω
20
°
C: 6.4 k
Ω
25
°
C: 5.3 k
Ω
30
°
C: 4.3 k
Ω
40
°
C: 3.1 k
Ω
Low-pressure shell scroll
type. Winding resitance
0.481 (20
°
C).
Low-pressure shell scroll type.
Winding resistance: each phase.
1.996 (20
°
C): P400 YMF-C
1.197 (20
°
C): P500 YMF-C
1
273+t
1
273
1
273+t
1
393
Application
Product code
Specification
Indoor unit
LEV
TH21
(Inlet air
temperature)
TH22
(Piping
temperature)
TH23
(Gas piping
temperature)
MC1
MC2
White
Red
Yellow Brown Blue
Orange
M
Perform a continuity
check using a tester.
Conductivity among
white, red and orange.
Conductivity among yel-
low, brown and blue.
Resistance value
check
Con-
nector
Pressure
0 to 30 kg/cm
2
G
(0 to 2.94 MPa)
Vout 0.5 to 3.5 V
Connector
GND (Black)
Vout (White)
Vc (DC 5 V) (Red)
1
273+t
1
273
63HS
Pressure
0 to 10 kg/cm
2
G
(0 to 0.98 MPa)
Vout 0.5 to 3.5 V
(0.3 V/kg/cm
2
, V/MPa)
Gnd (black)
Vout (white)
Vc (DC 5 V) (Red)
Con-
nector
63LS
Set to 30 kg/cm
2
G
(2.94 MPa) OFF.
R
120
= 7.465 k
Ω
B
25/120
= 4057
Rt =
7.465exp{4057( - )}
R
0
= 33 k
Ω
B
0/100
= 3965
R
t
=
33exp{3965( - )}
– 20
°
C: 92 k
Ω
– 10
°
C: 55 k
Ω
0
°
C: 33 k
Ω
10
°
C: 55 k
Ω
20
°
C: 13 k
Ω
30
°
C: 8.2 k
Ω
1
Detects high-pressure pressure.
2
Performs frequency control and high-
pressure protection.
1) Detects low-pressure.
2) Calculates the refrigerant circula-
tion configuration.
3) Protects the low pressure
1
Detects high-pressure.
2
Performs high-pressure protection.
1
Detects high-pressure pressure.
2
Performs high-pressure protection.
0
°
C: 698 k
Ω
60
°
C:
48 k
Ω
10
°
C: 413 k
Ω
70
°
C:
34 k
Ω
20
°
C: 250 k
Ω
80
°
C:
24 k
Ω
30
°
C: 160 k
Ω
90
°
C: 17.5 k
Ω
40
°
C: 104 k
Ω
100
°
C: 13.0 k
Ω
50
°
C: 70 k
Ω
110
°
C: 9.8 k
Ω
1
Detects low pressure saturation tem-
perature.
2
Performs frequency control and liq-
uid level of accumulator.
High
pressure
sensor
Low
pressure
sensor
Pressure
switch
Thermistor
63HS
63LS
63H1
62H2
TH11,12
(Outlet)
TH2 (Low
pressure
saturation
temperature)
Conductivity check
Resistance check
Resistance check
Summary of Contents for CITY MULTI P500YMF-C
Page 2: ......
Page 15: ... 13 CNFAN CNPOW CNFC2 CN15V1 CNDR1 CNIPM1 CNE CNDC1 FANCON board G A board ...
Page 16: ... 14 Y C board SNB board ...
Page 18: ... 16 RELAY 10 board RELAY 4 board ...
Page 22: ... 20 3 Electrical Wiring Diagram PURY P400 500YMF C ...
Page 91: ... 89 Motor Compressor G A board Red U V W N P White Black Black Capacitor C2 C3 Red IPM ...