–47–
<Initial start control timing chart>
Note 1: If the frequency of No. 1 compressor is above the specified level at the end of Step 2, the mode proceeds to
Step 3.
Note 2: At the completion of Step 2, if the frequency of No. 1 compressor is below the specified value and if Step 2 has
been completed less than 3 times, the process does not proceed to Step 3 but rather enters the Pause Step
and then repeats Step 2.
Note 3: At the completion of Step 2, if it has been completed more than 3 times, the mode will proceed to Step 3 even
if the frequency of No. 1 compressor is below the specified value.
30 minutes
Step 1
3
minutes
10 minutes
Step 2
5 minutes
Step 3
ON/OFF of
No.1 compressor
ON/OFF of
No.2 compressor
End of initial operation mode
Note 1
30 minutes
Step 1
3
minutes
10 minutes
Step 2
3
minutes
10 minutes
Step 2
Step 2
5 minutes
Step 3
Note 1
ON/OFF of
No.1 compressor
ON/OFF of
No.2 compressor
Note 2
End of initial operation mode
30 minutes
Step 1
3
minutes
10 minutes
Step 2
3
minutes
10 minutes
Step 2
3 times
3
minutes
10 minutes
Step 2
5 minutes
Step 3
Note 3
ON/OFF of
No.1 compressor
ON/OFF of
No.2 compressor
Note 2
End of initial operation mode
(Example 1)
(Example 2)
(Example 3)
Summary of Contents for CITY MULTI P500YMF-C
Page 2: ......
Page 15: ... 13 CNFAN CNPOW CNFC2 CN15V1 CNDR1 CNIPM1 CNE CNDC1 FANCON board G A board ...
Page 16: ... 14 Y C board SNB board ...
Page 18: ... 16 RELAY 10 board RELAY 4 board ...
Page 22: ... 20 3 Electrical Wiring Diagram PURY P400 500YMF C ...
Page 91: ... 89 Motor Compressor G A board Red U V W N P White Black Black Capacitor C2 C3 Red IPM ...