–143–
[4] Location of leaks: Outdoor unit (when heating)
1
Remove any refrigerant from the entire system (outdoor unit, extension piping and indoor units).
Reclaim the refrigerant; do not discharge it into the air.
2
Repair the leaks.
3
After the leaks are repaired, replace the dryer with a new one and extract all of the air from the entire system to
create a vacuum. Then, refill with refrigerant until it reaches the calculated specification (outdoor unit + extension
indoor units). Refer to “Chapter
6
” for more details.