16
2.2.2
Scope of the power supply for the transmission cable
To implement the AnyWire Bitty system, all conditions specified by the following calculation formulas 1) to 3) have to
be met.
(1) Description of calculation formula 1)
(a) Related constant of non-isolated slave modules (Ihin, Iho)
For non-isolated slave modules, current required for the internal control circuit and connected load is supplied
through the transmission cable (DP, DN).
Ihin(A)
= Current consumption of non-isolated input slave module/I/O combined slave module
= Current consumption of non-isolated input slave module/I/O combined slave Current consumption
of connected load (three-wire sensor)
Number of points
Iho(A)
= Current consumption of non-isolated output slave module
= Current consumption of non-isolated output slave Current consumption of connected load
Number of points
●
The 24VL and 0VL terminals of a slave module are used to supply the power to the connected load. For details, refer to
the manual for the slave module used.
●
For the current consumption of non-isolated slave modules, refer to the manual for the slave module used.
Item
Description
Calculation formula 1)
I(A) = (Ihin
m) + (Iho
n) + (Izdin
p) + (Izdo
q)
The maximum value of the transmission cable supply current
The number of connected modules by type: m, n, p, q
Calculation formula 2)
Vm(V) -
V(V)
20V
Calculation formula 3)
Vm(V) -
V(V)
The lowest limit of the allowable voltage range for connected load
Non-isolated slave module
Control circuit
Power supply
generation
Connected load
24VDC external
power supply
24V 0V
24V 0V
24VL
0VL
0
1
n
DN
DP
DN
DP
NZ2AW1C1BY
Summary of Contents for CC-Link-AnyWire Bitty Bridge
Page 1: ...CC Link AnyWire Bitty Bridge Module User s Manual NZ2AW1C1BY ...
Page 2: ......
Page 9: ...7 Memo ...
Page 14: ...12 Memo ...
Page 24: ...22 2 4 External Dimensions Unit mm 15 4 3 85 141 5 DIN rail 3 8 2 5 66 69 40 100 51 ...
Page 53: ...51 CHAPTER 10 CC LINK I O RESPONSE TIME 10 Memo ...
Page 73: ......