BC34
B
ATTERY
C
ABINET
10/13/2014
13
755-00114 R04
6.4
G
ENERAL
S
PECIFICATIONS
Cabinet Size:
32”W x 27”D x 67.3”H
Empty Cabinet Weight (approximately):
450 lbs.
Operating Temperature:
20°C to 25°C (68°F to 77°F) recommended for optimum battery
performance.
Ventilation:
Through ventilation slots front and rear. A minimum of four inches is required in
front and behind the cabinet. This refers to obstruction of ventilation only. Clearance around the
equipment should be as suggested by NEC and/or all applicable national and local codes.
Under certain conditions, batteries can vent potentially explosive gas (hydrogen).
Never enclose batteries or battery cabinets in a sealed room.
Batteries should be stored no longer than three months at 25°C (77°F) or lower
before recharging. Exceeding the recommended ambient storage temperature may
cause damage to the batteries.