14
3.2 Performance specifications
The performance specifications of the AJ65BTS-RPH module are
shown below.
Table 3.2 Performance specifications (1/2)
Item
Specifications
Station number
- (none)
CC-Link station
type
- (none)
Number of
occupied stations
0 (none)
Transmission rate
Can select from 156kbps / 625kbps / 2.5Mbps / 5Mbps / 10Mbps
No. of connectable
slave stations
The total number of modules connected to a trunk line and branch line
shall conform to the maximum number of connectable modules of the
master module used.
For details, refer to the user’s manual of the master modules used.
Max. No. of
modules connected
to the trunk line
64 (Refer to Section 2.3(2))
Connection position
Trunk
line side
No restriction (compliant with the CC-Link specifications)
Branch
line side
Connect to the end of the branch line (segment end)
Max. number of
stages connected
to configure
segment
AJ65BTS-RPH only (Refer to Section 2.3(3))
2nd stage
Combination of AJ65BTS-RPH and AJ65SBT-RPT (Refer to
Section 2.3 (4))
3rd stage
Combination of AJ65BTS-RPH and one of AJ65FBTA-RPH,
AJ65SBT-RPS/RPG, or AJ65BT-RPI (Refer to Section 2.3
(4))
2nd stage
Max. transmission
distance of each
segment
Varies according to transmission rate (Refer to Section 3.4.).
Terminating resistor
Trunk
line side
110
Ω
, or 130
Ω
can be selected.
Branch
line side
110
Ω
(built-in)
Terminal block
Spring clamp terminal block
Applicable cable
size
AWG #24 to 12,
φ
0.5 to 1.78mm single cable,
0.2 to 2.5mm
2
stranded cable
Applicable
solderless
terminal
Refer to table 3.3