27
Important
Important
In each segment, ensure to use the same type of CC-Link dedicated cables.
If different types of cables are used, normal data transmission will not be
assured.
Sur chaque segment, s'assurer qu'on utilise des câbles dédiés CC-Link du
même type.
Si les câbles utilisés sont de types différents, la transmission normale des
données ne peut être garantie.
POINT
POINT
• Ensure to connect the terminating resistances to both end modules of each
segment. In addition, connect them between DA and DB (DA1-DB1 and DA2-
DB2 for AJ65BT-RPI-10A/10B).
(The terminating resistances are furnished with the module.)
• The terminating resistances vary according to the type of cables in use.
For detail, refer to the User's Manual of the applicable master module.
• Connect the shield cable of the CC-Link dedicated cable to "SLD" of each
module, and ground both ends of the cable through "FG" to a class-D (class
3) ground.
SLD and FG are wired to each other inside the module.
• Ne pas oublier de raccorder la résistance terminale aux deux modules
d'extrémité sur chaque tronçon.De plus, établir la connexion entre DA et DB
(DA1-DB1 et DA2-DB2 pour AJ65BT-RPI-10A/10B).
(Les résistances terminales sont fournies avec le module.)
• Les résistances terminales diffèrent en fonction du type des câbles utilisés.
Pour le détail, voir le Manuel de l'utilisateur du module maître concerné.
• Raccorder le câble de blindage du câble dédié CC-Link sur "SLD" de chaque
module, et mettre à la terre les deux extrémités du câble via "FG" sur une terre
prise de terre de classe D (classe 3).
SLD et FG sont câblés entre eux à l'intérieur du module.