5. PROGRAMMING
MELSEC-A
5-4
(3) Initial
setting
Setting item
Description
CH. 1 sampling processing/travel average
processing designation flag (RY08)
Travel average processing
CH. 2 sampling processing/travel average
processing designation flag (RY09)
Travel average processing
All CH. batch “K” type thermocouple
selection flag (RY50)
“K” type thermocouple for all channels
Pt100 cold junction compensation disable
flag (RY57)
Cold junction compensation is performed by
the Pt100 temperature-measuring resistor.
Offset/gain value selection flag (RY77)
Factory setting
CH.1 Lower limit value (0.1
°
C units) (RWw0)
0
CH.1 Upper limit value (0.1
°
C units) (RWw1)
5000
CH.2 Lower limit value (0.1
°
C units) (RWw2)
0
CH.2 Upper limit value (0.1
°
C units) (RWw3)
5000
(4) Other
settings
Setting item
Description
CH. 1 conversion enable flag (RY00)
Conversion enable
CH. 2 conversion enable flag (RY01)
Conversion enable