3. SPECIFICATIONS
MELSEC-A
3-19
(2) Sampling
processing
Stores the detected temperature value and scaling value are stored in the remote register by
each sampling time.
1st storage
1st storage
2nd storage
3rd storage
2nd storage
3rd storage
The data transition inside the remote register
Sampling time
T
em
pe
ra
tu
re
[°C]
Time [ms]
Remote register
Detected
temperature
value
(3) Changes caused by altering sampling processing/travel average processing settings
<When changed from sampling processing
→
travel average processing>
The conversion completion flag is turned off for the corresponding channel.
After an average of four previously detected temperature values is calculated and stored to the
remote register, the conversion completion flag for the corresponding channel is turned on.
<When changed from travel average processing
→
sampling processing>
The conversion completion flag is turned off for the corresponding channel.
After the most recent detected temperature value is stored in the remote register, the conversion
completion flag for the corresponding channel is turned on.