4
D
E
F G
13-1/2
(340)
31-7/8 (811)
Check the pitch of the suspension bolt. (13-1/2 in.
×
32 in. (340 mm
×
811 mm)) (Fig.
2-6)
1. Thread washers
1
2
(supplied) and their nuts (procured locally) onto the sus-
pension bolt in advance.
* Do this in the following order (from the top): nut, insulated washer
2
, washer
without insulation
1
, two nuts.
* Position insulated washer
2
with the insulated surface pointing down, as in the
figure.
2. Lift the unit into place, aligned properly with the suspension bolt. Pass the bracket
between washers
1
and
2
, which are already in place, and secure it. Do the
same in all four places.
* Make sure the suspension bolt extends 3/4 in. (20 mm) or more from the surface
of the ceiling. Otherwise you will not be able to install the cover panel (sold sepa-
rately).
3. If the long opening in the bracket and opening in the ceiling do not align, adjust
them until they do.
4. Check that the four corners are all level, using a spirit level or clear plastic tubing
with water in it.
* Make sure that any slant in the unit after installation is less than 0.5 degrees
(approx. 1/4 in. (6 mm) on the long dimension of the unit).
5. Tighten all the nuts. (Fig. 2-7)
B
in. (mm)
in. (mm)
Fig. 2-6
A
Suspension bolt (3/8" or M10)
B
Ceiling surface
C
Nut (3/8" or M10)
D
Washer
2
(with insulation)
E
Washer
1
F
(Install with insulation facing down)
G
Measurement to upper face of bracket
A
Suspension bolt (3/8" or M10)
B
Clear plastic tubing
C
Underside of bracket
D
Secure front panel here
E
Make these surfaces are flush with each other (0 - 1/8 in. (0 - 3 mm))
Fig. 2-7
K
L
M
J
H
I
in. (mm)
in. (mm)
Fig. 2-4
Fig. 2-5
D
Ceiling panel
E
Rafter
F
Beam
G
Roof beam
H
Use inserts rated at 250-350 lbs (100-150 kg) each (procure locally)
I
Suspension bolts 3/8" (M10) (procure locally)
J
Steel reinforcing rod
K
C channel
L
Channel suspension bracket
M
M10 suspension bolt
2.4. Unit suspension procedures (Fig. 2-5)
Procure 3/8" bolts or M10 bolts locally.
• Adjust the length of the bolt’s protrusion from the ceiling surface beforehand.
*1. When using an extra upper nut in suspending the unit, in some cases you may
have to add it later.
A
Suspension bolt
B
Ceiling panel
C
Nut
D
Washer (with insulation)
2
E
Washer (without insulation)
1
2. Installing the indoor unit
1
Wooden structures (Fig. 2-4)
• Use tie beams (single storied houses) or second floor beams (two story houses) as
reinforcing members.
• Wooden beams for suspending air conditioners must be sturdy and their sides
must be at least 2-3/8 in. (6 cm) long if the beams are separated by not more than
35-7/16 in. (90 cm) and their sides must be at least 3-9/16 in. (9 cm) long if the
beams are separated by as much as 70-7/8 in. (180 cm). The size of the suspen-
sion bolts should be 3/8" (ø10). (The bolts do not come with the unit.)
• Use channel, duct and other parts procured locally to suspend the indoor unit.
2
Ferro-concrete structures
Secure the suspension bolts using the method shown, or use steel or wooden hang-
ers, etc. to install the suspension bolts.
A
C
D
E
C
*1
B
Min. 51/64(20)
Min. 1-3/16(30)
F
G
B
B
C
*
E
*
D
C
A
4-13/32(112)
Min.
51/64(20)
4-21/64
(110)
A
C
D E
4-21/64
(110)
Summary of Contents for Air-Conditioners For Building Application
Page 11: ......