background image

9

5. Electrical work

1

A

Fig. 5-7

AB

TB6

B

2) Connecting procedures (Fig. 5-7)

1

Connect the remote controller cord to the terminal block.

A

To TB5 on the indoor unit

B

TB6 (No polarity)

3) Temperature display setting

The initial temperature display setting is °C. Please change the setting to °F. Refer to
“Function selection of remote controller (Section 8)” in the operation manual for the
indoor unit.

4) Two remote controller setting

If two remote controllers are connected, set one to “Main” and the other to “Sub”. For
setting procedures, refer to “Function selection of remote controller” in the operation
manual for the indoor unit.

A

ON/OFF button

B

Test run display

C

Indoor temperature liquid
line temperature display

D

ON/OFF lamp

E

Power display

F

Error code display

Test run remaining time
display

G

Set temperature button

H

Mode selection button

I

Fan speed button

M

TEST button

Fig. 6-1

6. Test run

6.1. Before test run

s

After completing installation and the wiring and piping of the indoor and
outdoor units, check for refrigerant leakage, looseness in the power supply
or control wiring, wrong polarity, and no disconnection of one phase in the
supply.

s

Use a 500-volt megohmmeter to check that the resistance between the power
supply terminals and ground is at least 1.0 M

.

s

Do not carry out this test on the control wiring (low voltage circuit) termi-
nals.
 Warning:

Do not use the air conditioner if the insulation resistance is less than 1.0 M

.

Insulation resistance

6.2. Test run

The following 2 methods are available.

6.2.1. Using wired remote controller (Fig. 6-1)

1

Turn on the power at least 12 hours before the test run.

2

Press the [TEST] button twice. 

 “TEST RUN” liquid crystal display

3

Press the [Mode selection] button. 

 Make sure that wind is blown out.

4

Press the [Mode selection] button and switch to the cooling (or heating) mode.

 Make sure that cold (or warm) wind is blown out.

5

Press the [Fan speed] button. 

 Make sure that the wind speed is switched.

6

Check operation of the outdoor unit fan.

7

Release test run by pressing the [ON/OFF] button. 

 Stop

8

Register a telephone number.
The telephone number of the repair shop, sales office, etc., to contact if an error
occurs can be registered in the remote controller. The telephone number will be
displayed when an error occurs. For registration procedures, refer to the opera-
tion manual for the indoor unit.

Note:
• If an error code is displayed on the remote controller or if the air conditioner

does not operate properly, refer to the outdoor unit installation manual or
other technical materials.

• The OFF timer is set for the test run to automatically stop after 2 hours.
• During the test run, the time remaining is shown in the time display.
• During the test run, the temperature of the indoor unit refrigerant pipes is

shown in the room temperature display of the remote controller.

• When the VANE or LOUVER button is pressed, the message “NOT AVAIL-

ABLE” may appear on the remote controller display depending on the indoor
unit model, but this is not a malfunction.

˚F

˚F

SIMPLE

PAR-21MAA

ON/OFF 

FILTER

CHECK

OPERATION

CLEAR

TEST

TEMP.

MENU

BACK

DAY

MONITOR/SET

CLOCK

ON/OFF

TEST RUN
COOL, HEAT

A

F

C

E

D B

M

I

H G

7. Installing the grille

7.1. Checking the contents

• This kit contains the following parts.

Accessory name

Q’ty

Remark

1

Grille

1

2

Screw

6

M5 

×

 0.8 

×

 16

3

Screw

1

×

 16

7.2. Checks before setting in place

• Before installing the front panel, make sure the indoor unit is square with the ceiling

opening (or parallel to the angle between the wall and the ceiling).

• Check that the four points where the front panel will be secured are in contact with

the ceiling surface (see Fig. 7-1).

• Check that the insulation for the refrigerant pipes, drainage pipes, etc. is in place

and that wiring connections and arrangements are complete.

1

2

3

A

Points for securing the grille

B

Points for securing the grille

C

Indoor unit

D

Ceiling surface

E

Drainage pan

F

Places for securing front grille

G

Make sure these surfaces are
flush with each other 0 - 1/8 in.
(0 - 3 mm).

Fig. 7-1

A

B

C

F

G

E

D

Summary of Contents for Air-Conditioners For Building Application

Page 1: ...NSTALLATION MANUAL For safe and correct use please read this installation manual thoroughly before installing the air conditioner unit Air Conditioners For Building Application INDOOR UNIT PMFY P NBMU E ...

Page 2: ... install the indoor unit where such dripping can cause damage When installing the unit in a hospital or communications office be prepared for noise and electronic interference Inverters home appliances high fre quency medical equipment and radio communications equipment can cause the air conditioner to malfunction or breakdown The air conditioner may also affect medical equipment disturbing medica...

Page 3: ...heck window and will be needed later during servicing If the dimensions are not accurate when the grille is installed there may be gaps between it and the indoor unit This may result in dripping water or other problems When deciding on placement consider carefully the space around the ceiling and make your measurements generous Ceiling types and building construction differ Therefore you should co...

Page 4: ...D Secure front panel here E Make these surfaces are flush with each other 0 1 8 in 0 3 mm Fig 2 7 K L M J H I in mm in mm Fig 2 4 Fig 2 5 D Ceiling panel E Rafter F Beam G Roof beam H Use inserts rated at 250 350 lbs 100 150 kg each procure locally I Suspension bolts 3 8 M10 procure locally J Steel reinforcing rod K C channel L Channel suspension bracket M M10 suspension bolt 2 4 Unit suspension p...

Page 5: ...not contain any harmful contaminants such as sulfuric com pounds oxidants debris or dust Warning When installing or moving the air conditioner use only the specified refriger ant R410A to charge the refrigerant lines Do not mix it with any other refriger ant and do not allow air to remain in the lines Air enclosed in the lines can cause pressure peaks resulting in a rupture and other hazards P06 P...

Page 6: ... at the transparent check window and the outlet of the drainage pipe 4 Stop the test run Don t forget to turn off the power Fig 4 3 Fig 4 1 Fig 4 2 A Ceiling panel B Max 23 5 8 in 60 cm C Position of drain outlet D Make as short as possible Max 6 in 15 cm E Make as small as possible F Downward slope 1 100 or more G Make as great as possible Min 4 in 10 cm H Drainage pipe vertical section I Water b...

Page 7: ... the M1 and M2 on indoor unit TB5 to a M NET remote controller Non polarized 2 wire DC 24 to 30 V between M1 and M2 M NET remote controller A Terminal block for indoor transmission cable B Terminal block for outdoor transmission cable C Remote controller Constraints on transmission cable Fig 5 3 Longest wiring length L1 L2 L4 or L1 L3 or L2 L3 L4 less than 656 ft 200 m Length between indoor unit a...

Page 8: ...tion pitch 5 6 Remote controller For wired remote controller 1 Installing procedures Fig 5 5 1 Select an installing position for the remote controller The temperature sensors are located on both remote controller and indoor unit s Procure the following parts locally Two piece switch box Thin copper conduit tube Lock nuts and bushings 2 Seal the service entrance for the remote controller cord with ...

Page 9: ...eed button Make sure that the wind speed is switched 6 Check operation of the outdoor unit fan 7 Release test run by pressing the ON OFF button Stop 8 Register a telephone number The telephone number of the repair shop sales office etc to contact if an error occurs can be registered in the remote controller The telephone number will be displayed when an error occurs For registration procedures ref...

Page 10: ... press the intake grille on the place marked Push until you hear it snap into place 7 4 Checks after installing Check that there are no gaps between the indoor unit and the front panel and between the front panel and the ceiling surface If there are gaps the wind may come in and condensation may result Check that the air filter is in place 7 3 Installing the grille Open the intake grille by pressi...

Page 11: ......

Page 12: ...his manual before handing it to the customer This product is designed and intended for use in the residential commercial and light industrial environment HEAD OFFICE MITSUBISHI DENKI BLDG 2 2 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN Printed in Japan BG79U635H01 ...

Reviews: