Electronic trip relay

9

9

Electronic trip relay

The display shows the current and harmonics for real time monitoring. 
Moreover, the fault memory function is available so that it is possible to find out the 
reason of breaker trip.

Display (DP)

Option

ETR

ACB

Power

supply

Alarm

contact

output

513

544

P1

P2

N1

N2

NCT

Block diagram with NCT function

The Neutral CT is used for ground fault protection when the 3-pole breaker is 
used on a 3-phase 4-wire system and for the overcurrent protection on N phase. 
Please use this CT in combination with ground fault protection (GF). 
As for the outline dimensions, refer to page 34.
The length of the cable (attached) for NCT is 2 m.

Neutral CT (NCT) 

*Only use for AE V Series

Option

GF function block diagram (In case of 4-pole breaker)

ETR

ACB

Power

supply

Alarm

contact

output

513

544

P1

P2

60
50

40

30

20

Operating time (s)

Ground fault current (% of CT rating ln)

0.1

0.3

3.0

0.1

1.0

(s) 

10

5

4

3

2

1

.5

.05

.04

.03

.02

.4

.3

.2

.1

1
50

40

30

20

10

5

4

3

2

1

.5

.05

.04

.03

.02

.4

.3

.2

.1

10

20

50

100 125150 200

500

1000

Ground fault pick-up current: lg
In × 0.1-1.0 ±20% (step 0.1)

Ground fault time: Tg (Note)
0.1-0.15-0.3-0.5-0.8-1.5-3.0 (s) ±20%

Ground fault protection characteristic curve

Type name

ACB type

Rating ampere of current transformer (A)

NCT-06-V

AED630-CV

630

NCT-10-V

AED1000-CV

1000

NCT-12-V

AED1250-CV

1250

NCT-16-V

AED1600-CV

1600

Neutral Current Transformer type name

For outline dimensions, please refer to page 34.

Note) When Tg = “0.1” setting, operating time is 0.1 s ±50%.
 

When Tg = “0.15” setting, operating time is 0.15 s ±30%.

Specifications of display indication

Measuring items

Measuring

range

Display indication

Remark

Current 

(A)

Current of each phase

0 to 200% In

***** A (In = 630 A to 1600 A)

Indication of 1 to N phase concurrently

(Bar graph display is also available)

Maximum value

Harmonics

(HI)

Fundamental harmonics of each phase

0 to 100% In

***** A (In = 630 A to 1600 A)

Indication of 1 to N phase

Harmonics of each phase/degree (3

rd

, 5

th

, 7

th

, 9

th

)

Each phase total value

Each phase total distortion rate

***.* %

Content rate of each phase/degree

Fault

memory

Trip cause/Fault current

0 to 2000% In

LTD

STD

INST

***** A (0-19999 A)

***.* kA (20000 A and more)

0 to 200% In

GF

***** A

GF is an option

Elapsed time since tripping 

0 to 24:00

h: m

Time is recorded up to 24 hours

 Optional function for electronic trip relay

The electronic trip relay can be checked by this field test device when the
breaker is at the test position or the disconnect position. The breaker will be tripped 
when tested with this device in the “trip mode”.

Field test device

 (Y-2005)

Option

Test items

LTD, STD, INST, GF, PAL

Range of signal output

Voltage signal equivalent to 1% to 2500% of Rated current In (CT rating)

Dimensions

220 mm (W) × 150 mm (H) × 340 mm (D)

Time counter

0.000 to 999.999 s

Input voltage

100-240 V AC 50/60 Hz

Weight

4.5 kg

Y-2005 specification

Example of display indication

Time after tripping

“HH:MM”

Bar graph display

current (A)

Current (A)

Harmonics (HI)

Maximum current (A)

Trip cause

Fault current

Time after tripping

Trip cause

With this MCR switch, at the time of breaker closing from OFF to ON the INST (Instantaneous) 
characteristic works, and then after breaker is in closed (ON) position the INST characteristic becomes ineffective. 
This controlling function of INST characteristic is useful for the protection on the short-circuit fault at the time of 
closing and also for expanding the selective combination with branch breakers after closed.
MCR is equipped as standard.

MCR

Standard

The ground fault protection (GF) of several hundred amperes is available. 
This function can be selected for trip or alarm (no trip). Power supply is necessary 
for this function, even if there is not power supply, it can function at 0.2 × In or higher.

Ground fault protection (GF)

Option

Setting item

Mark

Adjustable setting range

Accuracy

Factory default value

GF pick-up current

Ig

0.1-0.2-0.3-0.4-0.5-0.6-0.7-0.8-0.9-

1.0

 × In

±20%

1.0

GF time

Tg

±20%

(Note)

3 s (TRIP)

Alarm output

Setting for TRIP: Self-holding/Setting for ALARM: Automatic reset

Setting for TRIP (Self-holding)

3

-1.5-0.8-0.5-0.3-0.15-<0.1 - <0.1-0.15-0.3-0.5-0.8-1.5-3 s

TRIP

ALARM

Note) When Tg = “0.1” setting, operating time is 0.1 s ±50%.
 

When Tg = “0.15” setting, operating time is 0.15 s ±30%.

(at 1.5 × Ig)

Trip cause

INST 

: Short circuit current trip.

STD 

: Large current in short time STD range.

LTD 

: Overcurrent in LTD range.

GF 

: Ground fault protection. (Option)

Summary of Contents for AED1000-CV

Page 1: ...son who has a specialized knowledge of electric construction and wiring http www mitsubishielectric com fa products lvd lvcb index html FA Global Site Eco Changes is the Mitsubishi Electric Group s environmental statement and expresses the Group s stance on environmental management Through a wide range of businesses we are helping contribute to the realization of a sustainable society MITSUBISHI L...

Page 2: ...Electric s vision Changes for the Better are possible for a brighter future 2 43 YOUR SOLUTION PARTNER Automation solutions Mitsubishi Electric offers a wide range of automation equipment from PLCs and HMIs to CNC and EDM machines A NAME TO TRUST Since its beginnings in 1870 some 45 companies use the Mitsubishi name covering a spectrum of finance com merce and industry TheMitsubishibrandnameisreco...

Page 3: ...ural disasters such as earthquakes lightning wind and water damages 6 Failure caused by reasons unpredictable based on scientific technology standards at the time of shipment from Mitsubishi Electric 7 Any other failure found not to be the responsibility of Mitsubishi Electric or that admitted not to be so by the user In addition the warranty applies only to the product delivered It does not apply...

Page 4: ...A 1000 A 1250 A 1600 A 50 kA 36 kA Specifications of AE V Series C class compared to AE SW Series Existing model World Super AE V Series C class is All New Mitsubishi Air Circuit Breaker series AE V Series C class is certified by the following parties China Compulsory Certificate system CCC Keuring van Elektrotechnische Materialen te Arnhem KEMA Certificate The adoption of the solenoid mechanism b...

Page 5: ...DC with output contacts Power Supply Note 2 Not available Communication Current display on ETR as standard Display Basic protection without display option Basic protection with current display Type of ETR unit Note 1 Without DP With DP Note 1 The above ETR units aren t modular structure Note 2 For details refer to page 23 SHT Shunt trip device is improved to Permanent SHT without controller as sta...

Page 6: ...tandard Note 2 This value indicates the operating time for the O operation at the time of short circuit interruption For the CO operation the value is 135 ms For the product with a UVT refer to page 16 Note 3 The mechanical service life includes the electrical service life Note 4 This is a guide of the service life when the regular maintenance specified by the manufacturer is performed Regular mai...

Page 7: ...0 CV AED1000 CV AED1250 CV AED1600 CV Type 1 Push button cover Counter Cylinder lock Terminal cover Door frame Dust cover Interphase barrier Mechanical accessories 6 Auxiliary switch Shunt trip device Under voltage trip device Electrical accessories 5 Cell switch Shorting b contact Lifting hook Safety shutter Safety shutter lock Mis insertion preventor Test jumper Drawout type accessories 4 Fixed ...

Page 8: ...e 1 While the voltage is applied to the input terminals C1 and C2 the SHT keeps the breaker in the open state and the closing operation is cancelled Therefore the SHT can be used as an interlock for locking the breaker in the open state Note 2 In case of double rating of rated voltage it is the value for the lower rating Example In case of 24 30 V DC it is operating time for 24 V DC Diode rectifie...

Page 9: ...g circuits The chattering time at the time of contact ON OFF is below 0 025 s Voltage V Current A Standard LAX Low capacity type LVAX Resistive load Inductive load Resistive load Inductive load AC 50 60 HZ 250 3 2 125 5 3 0 1 DC 250 0 2 0 2 125 0 4 0 4 30 4 3 0 1 Contacts max 5a5b 5a5b Change over sequence Breaker state a contact NO b contact NC ON ON OFF OFF OFF ON This is the contact that remote...

Page 10: ...us maintaining the correct sequence of operation of the external control circuit When ordering SBC with the same number of contacts as auxiliary switches LAXb will be provided Up to 5 SBCs can be mounted Shorting b contact SBC Option Operating sequence Main circuit Disconnected Connected Display position of drawout operation TEST CONNECT Change over sequence of SBC b contact ON OFF 2 This device e...

Page 11: ...tandard Lifting hook HP Option With the breaker taken out of its cradle this device enables the breaker to be electrically opened and closed and the operating sequence to be checked A cable of 3 m is equipped as standard shipment An extension cable 5 m is providable Test jumper TJ Option Both the main and control circuits are connected Normal in use condition The lock plate is protruding The main ...

Page 12: ...t and Pre alarm are reseted When the power supply module P3 or P4 is equipped the resetting from the control circuit terminal becomes possible Additionally this RESET button provides a lock function of LTD and STD characteristics on the INST testing with Mitsubishi Tester Y 2005 OCR alarm AL standard When the breaker is tripped by the overcurrent or ground fault protection GF this device continuou...

Page 13: ...L contact output turns on 20 Adjustable setting range Note The figure shows ETR type VS1DPGF Display and Ground fault protection are optional equipments In CT rating Ir Ig P 26 Iu Isd Ii Ip Load current LED 60 80 100 OVER Relation of setting dial The table and the figure include both optional display Pre alarm current OVER setting is Iu 1 15 Note O operation When Tsd 0 06 setting operating time is...

Page 14: ...ause Fault current 0 to 2000 In LTD STD INST A 0 19999 A kA 20000 A and more 0 to 200 In GF A GF is an option Elapsed time since tripping 0 to 24 00 h m Time is recorded up to 24 hours Optional function for electronic trip relay The electronic trip relay can be checked by this field test device when the breaker is at the test position or the disconnect position The breaker will be tripped when tes...

Page 15: ...arm and an other alarms A control supply is necessary for this function Setting procedure 1 Prepare a small flat tipped screwdriver 2 Insert the flat tipped screwdriver into the opening of the ETR cover Then lightly turn the screwdriver to the upside as shown in the left figure and the ETR cover will open 3 There are two kinds of switches for characteristics setting and for trip indicator reset Th...

Page 16: ...ll switch Terminal description Accessory Symbols Internal wiring External wiring userʼs wiring Control circuit connector drawout type On the drawout type the cables should have the length which allow the control circuit terminal block to be moved to the left or right by 5 mm When a coil load is connected in the same control circuit as the ETR surge absorbers are required to absorb the surge voltag...

Page 17: ...panel center 85 85 85 50 4P 3P Outline of breaker Neutral pole left option 85 85 85 Neutral pole right standard 15 Outline of breaker 4P 3P Operating panel center 85 85 85 Neutral pole right standard 15 Outline of breaker 4P 3P Operating panel center 15 Outline of breaker 4P 3P Operating panel center Neutral pole left option 85 85 85 85 85 85 Neutral pole left option 15 Outline of breaker 4P 3P Op...

Page 18: ...hould be secured firmly using the values in the below table as a reference Max distance between the fixing support and ACB conductor strip should be less than 200 mm When selecting conductors to be connected to AE V breakers ensure that they have a sufficient current capacity Refer to the following table ACB body 3 m 2 m The above table shows the suitable connecting conductor size based on IEC 609...

Page 19: ...l resistance mΩ Reactance mΩ Power consumption W AED630 CV Fixed type 0 017 0 11 7 Drawout type 0 037 0 15 15 AED1000 CV Fixed type 0 017 0 11 17 Drawout type 0 037 0 15 37 AED1250 CV Fixed type 0 017 0 11 27 Drawout type 0 037 0 15 58 AED1600 CV Fixed type 0 017 0 11 44 Drawout type 0 037 0 15 95 The values are typical values per pole in unused condition Please regard it as a reference Standard A...

Page 20: ...0 23 50 35 50 NF630 CW 50 19 50 28 50 NV630 CW 50 19 50 28 50 NF800 CEW 50 19 50 26 50 NF125 RGV 150 27 50 50 50 50 NF125 UV 200 39 50 50 50 50 NF250 RGV 150 14 50 40 50 50 50 NF250 UV 200 16 50 50 50 50 NF400 UEW 200 9 5 50 14 50 19 50 28 50 NF800 UEW 200 19 50 24 50 AED CV AED630 CV AED1000 CV AED1250 CV AED1600 CV 50 50 50 50 NF32 SV 2 5 2 5 2 5 2 5 2 5 NV32 SV 5 5 5 5 5 NF63 SV 7 5 7 5 7 5 7 5...

Page 21: ...V AC P 14 Main circuit terminal Horizontal Horizontal HT Horizontal Vertical HV Horizontal Front HF Vertical Vertical VT Vertical Horizontal VH Vertical Front VF Front Front FT Front Horizontal FH Front Vertical FV Equipment type Ambient temperature 40 C Standard FIXED DRAW OUT Others C 3 ø 3 W Neutral CT NCT 3 ø 4 W Electronic trip relay ETR With ETR BARE without ETR Note 3 Note 4 Type NA Without...

Page 22: ...n Germany 49 0 2102 4860 Greece KALAMARAKIS SAPOUNAS S A IONIAS NEROMILOU STR CHAMOMILOS ACHARNES ATHENS 13678 Greece 30 2102 406000 UTECO 5 MAVROGENOUS STR 18542 PIRAEUS Greece 30 211 1206 900 Hungary Meltrade Ltd Fertö utca 14 HU 1107 Budapest Hungary 36 0 1 431 9726 India Mitsubishi Electric India Private Limited Mitsubishi Electric India Private Limited Pune Sales Office 2nd Floor Tower A B Cy...

Reviews: