background image

5000

4000

3000

2000

1000

500

400

300

200

100

60
50

40

30

20

Operating time (s)

Current (%)

(s) 

(min) 

(h) 

10

5

4

3

2

1

.5

.05

.04

.03

.02

.01

.4

.3

.2

.1

1

2

10

15

30

40

1

20

8

6

4

50

40

30

20

10

5

4

3

2

1

.5

.05

.06

.04

.03

.02

.01

.4

.3

.2

.1

1

2

5

10

20

50

100 125 150 200

500

1000 1600 2000

5000

10000

INST/MCR pick-up current: Ii
Ir × 2-4-6-8-10-12-16 ±15%

Max. breaking time (Note 3)

I

2

t OFF

I

2

t ON 

(ramp)

With MCR

STD time: Tsd (Note 1) (Note 2)
0.06-0.1-0.2-0.3-0.4-0.5 (s) ± 20%

(at Isd × 1.5)

Ir × 0.8-1.0 (step 0.02)

Uninterrupted current: Iu

LTD pick-up 1.05 × Iu…Non pick-up

1.25 × Iu…Pick-up

STD pick-up current: Isd
Ir × 1.5-2-2.5-3-4-5-6-7-8-9-10 ±15%

Pre-alarm time: Tp
T

L

/2 ± 20% (at Iu × 2)

Pre-alarm current: Ip
Iu × 0.68-1.0 (step 0.04) - OVER ±10%

LTD time: T

L

12-25-50-100-150 (s) ± 20%

(at Iu × 2)

24

25

Electronic trip relay

9

9

Electronic trip relay

No.

Setting item

Mark

Adjustable setting range

Accuracy

Factory default

value

A

Current setting

Ir

0.5-

1.0

 (step 0.05) × In (CT rating)

1.0

K

Uninterrupted current

Iu

0.8-

1.0

 × Ir (step 0.02), Pick-up current: 1.15 × Iu

1.05 × Iu…Non Pick-up

1.25 × Iu…Pick-up

1.0

L

LTD time

T

L

12-25-50-100-

150 

s at Iu × 2

±20%

150

M

STD pick-up current

Isd

1.5-2-2.5-3-4-5-6-7-8-9-

10

 × Ir

±15%

10

N

STD time

Tsd

 

±20%

(Note)

0.5 (I

2

t ON)

J

INST/MCR

pick-up current

Ii

±15%

16 (INST)

G

Pre-alarm current

Ip

Iu × 0.68-1.0 (step 0.04) -

OVER

±10%

OVER

Pre-alarm time

Tp

1/2 T

L

 at Iu × 2 (after 1/2 T

L

, PAL contact output turns on.)

±20%

Adjustable setting range

Note) The figure shows ETR type: VS1DPGF. 
 

Display and Ground fault protection are optional equipments.

In (CT rating)

Ir

Ig

 (P.26)

Iu

Isd

Ii

Ip

Load current LED

(60, 80, 100%, OVER)

Relation of setting dial

The table and the figure include both optional display.
Pre-alarm current “OVER” setting is Iu × 1.15.
Note)

 

(O operation) When Tsd = “0.06” setting, operating time is 0.04-0.1 s.

 

 

When Tsd = “0.1” setting, operating time is 0.1 s ±50%.

(CO operation) When Tsd = “0.06, 0.1” setting, operating time is 0.04-0.15 s.

16

-12-10-8-6-4-2-2-4-6-8-10-12-16 × Ir

(INST)

(MCR)

Current setting dial

A

INST/MCR pick-up current setting dial

J

Load current LED

B

Uninterrupted current setting dial

K

RUN LED

C

LTD time setting dial

L

ERR. LED

D

STD pick-up current setting dial

M

Pre-alarm LED

E

STD time setting dial

N

Trip indicator LED

F

Ground fault protection setting module dial

O

Pre-alarm current setting dial

G

TEST terminal

I

Frequency setting switch

H

RESET button (TEST L/S LOCK button)

P

 For general purpose: Type S1

0.5

-0.4-0.3-0.2-0.1-0.06-0.06-0.1-0.2-0.3-0.4-0.5 s

(I

2

t ON)

 (I

2

t OFF)

at Isd × 1.5

Operating characteristic curve (for general purpose: Type S1)

Current  LTD pick-up, Ip … % of Uninterrupted current Iu
 

Iu, Isd, Ii  ………… % of Current setting Ir

Note 1) (O operation) When Tsd = “0.06” setting, operating time is 0.04-0.1 s.

 

When Tsd = “0.1” setting, operating time is 0.1 s ±50%. 

(CO operation) When Tsd = “0.06, 0.1” setting, operating time is 0.04-0.15 s.

Note 2) I

2

t is selectable: ON or OFF.

Note 3) When CO operation, max. breaking time is 0.135 s.

Summary of Contents for AED1000-CV

Page 1: ...son who has a specialized knowledge of electric construction and wiring http www mitsubishielectric com fa products lvd lvcb index html FA Global Site Eco Changes is the Mitsubishi Electric Group s environmental statement and expresses the Group s stance on environmental management Through a wide range of businesses we are helping contribute to the realization of a sustainable society MITSUBISHI L...

Page 2: ...Electric s vision Changes for the Better are possible for a brighter future 2 43 YOUR SOLUTION PARTNER Automation solutions Mitsubishi Electric offers a wide range of automation equipment from PLCs and HMIs to CNC and EDM machines A NAME TO TRUST Since its beginnings in 1870 some 45 companies use the Mitsubishi name covering a spectrum of finance com merce and industry TheMitsubishibrandnameisreco...

Page 3: ...ural disasters such as earthquakes lightning wind and water damages 6 Failure caused by reasons unpredictable based on scientific technology standards at the time of shipment from Mitsubishi Electric 7 Any other failure found not to be the responsibility of Mitsubishi Electric or that admitted not to be so by the user In addition the warranty applies only to the product delivered It does not apply...

Page 4: ...A 1000 A 1250 A 1600 A 50 kA 36 kA Specifications of AE V Series C class compared to AE SW Series Existing model World Super AE V Series C class is All New Mitsubishi Air Circuit Breaker series AE V Series C class is certified by the following parties China Compulsory Certificate system CCC Keuring van Elektrotechnische Materialen te Arnhem KEMA Certificate The adoption of the solenoid mechanism b...

Page 5: ...DC with output contacts Power Supply Note 2 Not available Communication Current display on ETR as standard Display Basic protection without display option Basic protection with current display Type of ETR unit Note 1 Without DP With DP Note 1 The above ETR units aren t modular structure Note 2 For details refer to page 23 SHT Shunt trip device is improved to Permanent SHT without controller as sta...

Page 6: ...tandard Note 2 This value indicates the operating time for the O operation at the time of short circuit interruption For the CO operation the value is 135 ms For the product with a UVT refer to page 16 Note 3 The mechanical service life includes the electrical service life Note 4 This is a guide of the service life when the regular maintenance specified by the manufacturer is performed Regular mai...

Page 7: ...0 CV AED1000 CV AED1250 CV AED1600 CV Type 1 Push button cover Counter Cylinder lock Terminal cover Door frame Dust cover Interphase barrier Mechanical accessories 6 Auxiliary switch Shunt trip device Under voltage trip device Electrical accessories 5 Cell switch Shorting b contact Lifting hook Safety shutter Safety shutter lock Mis insertion preventor Test jumper Drawout type accessories 4 Fixed ...

Page 8: ...e 1 While the voltage is applied to the input terminals C1 and C2 the SHT keeps the breaker in the open state and the closing operation is cancelled Therefore the SHT can be used as an interlock for locking the breaker in the open state Note 2 In case of double rating of rated voltage it is the value for the lower rating Example In case of 24 30 V DC it is operating time for 24 V DC Diode rectifie...

Page 9: ...g circuits The chattering time at the time of contact ON OFF is below 0 025 s Voltage V Current A Standard LAX Low capacity type LVAX Resistive load Inductive load Resistive load Inductive load AC 50 60 HZ 250 3 2 125 5 3 0 1 DC 250 0 2 0 2 125 0 4 0 4 30 4 3 0 1 Contacts max 5a5b 5a5b Change over sequence Breaker state a contact NO b contact NC ON ON OFF OFF OFF ON This is the contact that remote...

Page 10: ...us maintaining the correct sequence of operation of the external control circuit When ordering SBC with the same number of contacts as auxiliary switches LAXb will be provided Up to 5 SBCs can be mounted Shorting b contact SBC Option Operating sequence Main circuit Disconnected Connected Display position of drawout operation TEST CONNECT Change over sequence of SBC b contact ON OFF 2 This device e...

Page 11: ...tandard Lifting hook HP Option With the breaker taken out of its cradle this device enables the breaker to be electrically opened and closed and the operating sequence to be checked A cable of 3 m is equipped as standard shipment An extension cable 5 m is providable Test jumper TJ Option Both the main and control circuits are connected Normal in use condition The lock plate is protruding The main ...

Page 12: ...t and Pre alarm are reseted When the power supply module P3 or P4 is equipped the resetting from the control circuit terminal becomes possible Additionally this RESET button provides a lock function of LTD and STD characteristics on the INST testing with Mitsubishi Tester Y 2005 OCR alarm AL standard When the breaker is tripped by the overcurrent or ground fault protection GF this device continuou...

Page 13: ...L contact output turns on 20 Adjustable setting range Note The figure shows ETR type VS1DPGF Display and Ground fault protection are optional equipments In CT rating Ir Ig P 26 Iu Isd Ii Ip Load current LED 60 80 100 OVER Relation of setting dial The table and the figure include both optional display Pre alarm current OVER setting is Iu 1 15 Note O operation When Tsd 0 06 setting operating time is...

Page 14: ...ause Fault current 0 to 2000 In LTD STD INST A 0 19999 A kA 20000 A and more 0 to 200 In GF A GF is an option Elapsed time since tripping 0 to 24 00 h m Time is recorded up to 24 hours Optional function for electronic trip relay The electronic trip relay can be checked by this field test device when the breaker is at the test position or the disconnect position The breaker will be tripped when tes...

Page 15: ...arm and an other alarms A control supply is necessary for this function Setting procedure 1 Prepare a small flat tipped screwdriver 2 Insert the flat tipped screwdriver into the opening of the ETR cover Then lightly turn the screwdriver to the upside as shown in the left figure and the ETR cover will open 3 There are two kinds of switches for characteristics setting and for trip indicator reset Th...

Page 16: ...ll switch Terminal description Accessory Symbols Internal wiring External wiring userʼs wiring Control circuit connector drawout type On the drawout type the cables should have the length which allow the control circuit terminal block to be moved to the left or right by 5 mm When a coil load is connected in the same control circuit as the ETR surge absorbers are required to absorb the surge voltag...

Page 17: ...panel center 85 85 85 50 4P 3P Outline of breaker Neutral pole left option 85 85 85 Neutral pole right standard 15 Outline of breaker 4P 3P Operating panel center 85 85 85 Neutral pole right standard 15 Outline of breaker 4P 3P Operating panel center 15 Outline of breaker 4P 3P Operating panel center Neutral pole left option 85 85 85 85 85 85 Neutral pole left option 15 Outline of breaker 4P 3P Op...

Page 18: ...hould be secured firmly using the values in the below table as a reference Max distance between the fixing support and ACB conductor strip should be less than 200 mm When selecting conductors to be connected to AE V breakers ensure that they have a sufficient current capacity Refer to the following table ACB body 3 m 2 m The above table shows the suitable connecting conductor size based on IEC 609...

Page 19: ...l resistance mΩ Reactance mΩ Power consumption W AED630 CV Fixed type 0 017 0 11 7 Drawout type 0 037 0 15 15 AED1000 CV Fixed type 0 017 0 11 17 Drawout type 0 037 0 15 37 AED1250 CV Fixed type 0 017 0 11 27 Drawout type 0 037 0 15 58 AED1600 CV Fixed type 0 017 0 11 44 Drawout type 0 037 0 15 95 The values are typical values per pole in unused condition Please regard it as a reference Standard A...

Page 20: ...0 23 50 35 50 NF630 CW 50 19 50 28 50 NV630 CW 50 19 50 28 50 NF800 CEW 50 19 50 26 50 NF125 RGV 150 27 50 50 50 50 NF125 UV 200 39 50 50 50 50 NF250 RGV 150 14 50 40 50 50 50 NF250 UV 200 16 50 50 50 50 NF400 UEW 200 9 5 50 14 50 19 50 28 50 NF800 UEW 200 19 50 24 50 AED CV AED630 CV AED1000 CV AED1250 CV AED1600 CV 50 50 50 50 NF32 SV 2 5 2 5 2 5 2 5 2 5 NV32 SV 5 5 5 5 5 NF63 SV 7 5 7 5 7 5 7 5...

Page 21: ...V AC P 14 Main circuit terminal Horizontal Horizontal HT Horizontal Vertical HV Horizontal Front HF Vertical Vertical VT Vertical Horizontal VH Vertical Front VF Front Front FT Front Horizontal FH Front Vertical FV Equipment type Ambient temperature 40 C Standard FIXED DRAW OUT Others C 3 ø 3 W Neutral CT NCT 3 ø 4 W Electronic trip relay ETR With ETR BARE without ETR Note 3 Note 4 Type NA Without...

Page 22: ...n Germany 49 0 2102 4860 Greece KALAMARAKIS SAPOUNAS S A IONIAS NEROMILOU STR CHAMOMILOS ACHARNES ATHENS 13678 Greece 30 2102 406000 UTECO 5 MAVROGENOUS STR 18542 PIRAEUS Greece 30 211 1206 900 Hungary Meltrade Ltd Fertö utca 14 HU 1107 Budapest Hungary 36 0 1 431 9726 India Mitsubishi Electric India Private Limited Mitsubishi Electric India Private Limited Pune Sales Office 2nd Floor Tower A B Cy...

Reviews: