Technical information
12
12
Technical information
Arc space
When a short-circuit current is interrupted, discharged hot gas blows out from the exhaust port of the arc chute chamber,
so provide a clearance as shown in the following table.
Service conditions
1. Normal service condition
Under ordinary conditions that the following normal working
conditions are all satisfied, the AE V Series air circuit breaker
may be used unless otherwise specified.
1. Ambient temperature
A range of +40°C max. to -5°C min. is recommended.
And the average over 24 hours must not 35°C.
2. Altitude
2000 m (6600 feet) or less
3. Environmental conditions
The air must be clean, and the relative humidity must be 85%
or less at +40°C max. Do not use and store the product in
atmospheres with sulfide gas and ammonia gas etc.
(H
2
S
≤
0.01 ppm, SO
2
≤
0.1 ppm, NH
3
≤
0.25 ppm.)
4. Installation conditions
When installing the AE V Series air circuit breaker, refer to the
installation instructions in the catalogue and instruction manual.
5. Storage temperature
A range of max. +60°C to min. -20°C is recommended to
bestored.
And the average over 24 hours must not 35°C.
6. Guideline for replacement
Within approx. 15 years. Please refer to the instruction manual.
2. Special service conditions
In case of special service condition, the service life may become
shorter in some cases.
1. Special environmental conditions
High temperature and/or high humidity
Corrosive gas
2. High ambient temperature
If the ambient temperature e40°C, the uninterrupted
current rating will be reduced. Since the derating value is
different depending on the applicable standard, refer to
page 37.
3. High altitude
Since the heat radiation rate is reduced for use at the 2000 m
or higher, accordingly the operating voltage, continuous
current capacity, and breaking capacity are derated.
Moreover, the insulation durability is also decreased owing
to the atmospheric pressure.
Please inquire us for further details.
B
B
A
C
A
D
Note 1) 300 mm or more clearance is necessary to inspect the arc chute chamber and contacts.
Note 2) The wiring space required for the control terminal block.
Type
AED630-CV to AED1600-CV
Applicable voltage
500 V AC or less
Fixed type
A
0 (Note 1)
B
50
C
162
D
50 (Note 2)
Drawout type
A
0
B
50
C
240
D
50 (Note 2)
Dimensions
(mm)
Electrical equipment, appliances, or screen
Mounting
surface
Side
plate
Type
Connections
Internal resistance (mΩ)
Reactance (mΩ)
Power consumption (W)
AED630-CV
Fixed type
0.017
0.11
7
Drawout type
0.037
0.15
15
AED1000-CV
Fixed type
0.017
0.11
17
Drawout type
0.037
0.15
37
AED1250-CV
Fixed type
0.017
0.11
27
Drawout type
0.037
0.15
58
AED1600-CV
Fixed type
0.017
0.11
44
Drawout type
0.037
0.15
95
The values are typical values per pole (in unused condition). Please regard it as a reference.
Standard
Ambient temperature
AED630-CV
AED1000-CV
AED1250-CV
AED1600-CV
IEC 60947-2
(Standard 40°C)
40°C
630
1000
1250
1600
45°C
560
1000
1250
1600
50°C
500
1000
1250
1560
55°C
500
1000
1250
1500
60°C
440
1000
1200
1430
(A)
Deratings of Max. rated current by ambient temperature (Horizontal connection)
Table
2
Standard
Ambient temperature
AED630-CV
AED1000-CV
AED1250-CV
AED1600-CV
IEC 60947-2
(Standard 40°C)
40°C
630
1000
1250
1600
45°C
560
1000
1250
1600
50°C
500
1000
1250
1440
55°C
–
–
–
–
60°C
–
–
–
–
(1) The above table shows the maximum rated current per each ambient temperature for drawout type breaker with vertical connection (at brandnew product), when breaker and bus bar are installed in open air.
(2) Connection bus bar is according to IEC 60947-1. As for ambient temperature exceeding 60°C, please inquire us.
(3) The above table shows the maximum rated current at the ambient temperature.
(4) The above table shows the values calculated by the values measured under the test conditions specified in the IEC 60947-2, which are not actual values. With the circuit breaker mounted to the panel,
verify the values under the test conditions specified in the IEC 61439-1 and others.
Note) Set the proper values using the assembly verification in consideration of the influence of the heat of other devices in the panel, heat capacity of the connecting conductor, supply and exhaust, and air
convection in the panel.
In case extension, display (DP1) are attached, the following derating values shown in this table are applied.
(A)
Deratings of Max. rated current by ambient temperature with Display
Table 3
Internal resistance, reactance and power consumption (per pole)
Standard
Ambient temperature
AED630-CV
AED1000-CV
AED1250-CV
AED1600-CV
IEC 60947-2
(Standard 40°C)
40°C
630
1000
1250
1600
45°C
560
1000
1250
1600
50°C
500
1000
1250
1600
55°C
500
1000
1250
1590
60°C
440
1000
1250
1540
(A)
Deratings of Max. rated current by ambient temperature (Vertical connection)
Table
1
Deratings by ambient temperature
Precautions on installation
Grounding terminal
Unless otherwise specified, ground a grounding terminal for safety.
Possible position
Screw size
Tightening torque (N·m)
M12
45 ±5
Tightening torque
Installation direction