E-11
ENGLISH
Take out the drawout handle from the circuit
breaker.
Turn the drawout handle to change the drawout
position from CONNECT to DISCONNECT.
Regarding how to operate the drawout handle,
refer to section 6.3.
6.2.2 Operating method of the drawout type
6.3 CONNECT
→
DISCONNECT position
1. Keeping the OFF button pushed, insert the
drawout handle.
2. Push the lock plate fully until it is latched to
release the lock.
(Prohibition)
Do not insert the drawout handle forcibly
when the OFF button is not pushed.
Doing so can cause damage to the circuit
breaker.
(Note)
a. If the lock plate is not fully released,
turn the drawout handle to right and
left a little.
b. Be sure to push the lock plate fully to
the release position. Otherwise the
drawout position indicator may not
function correctly.
c. Do not perform the drawout operation
while the lock plate is protruding.
CONNECT position
2
DISCONNECT
TEST
CONNECT
Push
Lock plate
Lock position
Latch
Release position
Cover
Insert
Drawout
handle
OFF button
OFF button
1
1
2
Keep pushing