6 - 8 6 - 8
MELSEC-GOT
6 HANDLING
(2) Grounding the ground cable
Manufacture the cable used with the GOT with the following method.
When manufacturing the cable, a ferrite core, cable clamp and cable shielding
material are required.
The cable clamp used by Mitsubishi Electric for the EMC specification
compatibility test is shown below.
•
TDK brand ZCAT3035-1330 Ferrite Core
•
TDK brand ZCAT2436-1330 Ferrite Core
•
Mitsubishi Electric Model AD75CK cable clamp
•
Japan Zipper Tubing Co., Ltd. Zipper tube SHNJ type
a) BUS connection cable
1) For A8GT-C100/200/300EXSS, A8GT-C100/200/300BS.
•
Cut the connection wire protruding from both ends of the cable to the
lengths shown below.
•
Peel the sheath (with the length shown below) at both ends of the
cable, and expose the shield braided wire for grounding.
130
130
GOT side
PLC/GOT side
Ferrite Core
(ZCAT3035-1330)
Within 360
Within 360
40
40
Unit : mm (inch)
Ground wires
(280mm
(11.0inch))
(14.17)
(1.57)
(1.57)
(14.17)
(5.12)
(5.12)
2) For other cables between GOT and base unit
•
Wind cable shield material around the cable, and pull out the
grounding braided wire of the cable shield material with the length
shown below.
•
Pass the grounding braided wire on the programmable logic controller
side through the core.
Within 150
130
GOT side
PLC side
Unit : mm (inch)
Grounding braided
wire(50mm(1.97inch))
Grounding braided
wire(200mm(7.87inch))
Cable shield material
Ferrite Core
(ZCAT3035-1330)
(5.12)
(5.90)
Within 150
130
(5.12)
(5.90)