(N) Operation via communication and its settings
21
2
GROUP
N
Ethernet function selection (Pr.1427 to Pr.1429)
Refer to the Instruction Manual of the device connected via Ethernet, and set
Pr.1427 to Pr.1429 Ethernet function
selection 1 to 3
according to the application and protocol.
A communication socket is provided only for the selected application.
If both application and protocol settings are identical in
Pr.1427 to Pr.1429
, the priority of the setting is defined as follows:
Pr.1427
>
Pr.1428
>
Pr.1429
.
(Example) When
Pr.1427
= "5001",
Pr.1428
= "5006",
Pr.1429
= "5013", "5001" and "5013" are valid.
To connect the inverter and FR Configurator2 via the MELSOFT / FA product for Ethernet communication, set "5001 (initial value)" or "5002"
according to the protocol type (UDP/IP or TCP/IP) in any of
Pr.1427 to Pr.1429
.
When the inverter is connected with other equipment via a hub, and if the communication between the other equipment and the hub is
interrupted and resumed, the communication between the inverter and the other equipment may not be established depending on the
specifications of the hub. To re-establish communication with the other equipment, reset the inverter to forcefully close the connection. (Setting a
shorter time in
Pr.1455 Keepalive time
is also effective as a preventive measure (refer to
).)
For details, refer to the Instruction Manual of FR Configurator2.
Communication speed and full-duplex/half-duplex selection (Pr.1426)
Set the communication speed and the communication mode (full-duplex/half-duplex) in
Pr.1426 Link speed and duplex
mode selection
.
If the operation is not performed properly in the initial setting (
Pr.1426
= "0"), set
Pr.1426
according to the specifications of the
connected hub.
Pr.1427 to Pr.1429
setting
Application
Protocol
Number of
connectable clients
Refer to
page
502
Modbus/TCP
TCP/IP
3
5000
MELSOFT / FA product connection
UDP/IP
No limit
5001 (
Pr.1427
initial value)
5002
TCP/IP
5006
UDP/IP
No limit
5007
TCP/IP
5008
UDP/IP
No limit
5010
SLMP
UDP/IP
No limit
5011
5012
TCP/IP
5013
45237 (
Pr.1428
setting)
iQSS
UDP/IP
No limit
61450
CC-Link IE Field Network Basic
UDP/IP
No limit
9999 (
Pr.1429
initial value)
Unselected
—
Pr.1426 setting
Communication speed
Full-duplex/half-
duplex system
Remarks
0 (initial value)
Automatic negotiation
Automatic negotiation
The communication speed and the communication mode
(half-duplex/full-duplex) are automatically negotiated to
ensure the optimum setting.
1
100 Mbps
Full-duplex
—
2
100 Mbps
Half-duplex
—
3
10 Mbps
Full-duplex
—
4
10 Mbps
Half-duplex
—