7. COMMUNICATION THAT DO NOT REQUIRE
THE SEQUENCE PROGRAM
MELSEC-A
7-29
7.1.24 Program
stop
(Reset:
Server)
Use "Reset" service to STOP the sequence program from the client.
This can only be executed when the PC CPU status is Operational or Partially Operational. (Use
Status service to check the status.)
This can only be executed when the ProgramInvocation is in the STOPPED status. (Use GetOD to
check the status.)
PI status change
PI
status
before
execution
NON-EXISTENT IDLE
RUNNING STOPPED
Status after execution
×
×
×
IDLE
Use the GetOD service to check the PI status.
[Parameters required by the client]
•
Access Specification
Specify the Index or Name of the Program Invocation to be stopped.
Access Specification
Setting value
Index PI
Index
PI Name
PI Name
[Server (AJ71PB96F/A1SJ71PB96F) answer parameters]
None