-110-
(5)
Dry operation
Note: 1
When indoor unit inlet temperature exceeds 18˚C, outdoor unit (compressor) and indoor unit fan start intermittent operations
synchronously. Operations of outdoor unit, indoor unit LEV and solenoid valve accompanying compressor are the same as
those in cooling operations.
Note: 2
Thermostat is always kept on in test run, and indoor and outdoor unit intermittent operation (ON) time is a little longer than
normal operations.
YES
NO
YES
NO
Normal operations
Thermostat ON
Stop
Dry operations
4-way valve OFF
Test run start
Note: 2
Thermostat ON
Inlet temp. 18˚C
Note: 1
Variable capacity unit
1. Inverter output 0 Hz
2. Indoor unit LEV, SLEV,
LEV1 full closed
3. Solenoid valve OFF
4. Outdoor unit fan stop
5. 52C2 OFF
6. F = 0 after 6 minutes 52C1 OFF
Constant capacity unit
1. 52C OFF
2. Outdoor unit fan stop
3. LEV1, LEV2 full closed
4. Solenoid valve OFF
1. Outdoor unit (Compressor) intermit-
tent operations
2. Indoor unit fan intermittent opera-
tions
(Synchronized with compressor: low
speed / OFF operations)