-64-
(14) Operation Mode
1) Operating modes of the indoor unit
The following five modes can be set by the remote control.
1
Cooling mode
2
Heating mode
3
Dry mode
4
Fan mode
5
Stop mode
2) Operating modes of the outdoor unit
The following are the 3 modes for the outdoor unit.
1
Cooling mode
All indoor units are operated in cooling mode
2
Heating mode
All indoor units are operated in heating mode
3
Stop mode
All indoor units are in fan or stop mode
Note : If the outdoor unit has been in the cooling mode and the other indoor units (in stop, fan, thermostat off) are
to the heating mode, those indoor units will not be operated and the heating indicator will be flashed
remote controller. The reverse also applies when the outdoor unit is operated in the heating mode
the
the cooling indicator will be flashed on the remote controller.
and
Caution
During emergency operation, only marked percentage of indoor units can be operated during emergency operation.
In case, more than
marked percentage of indoor units are operated, over than the percentage of indoor units
would be on the stand-by mode.
Codes for which emergency operation is
possible.
Emergency Mode
Pattern
Codes for
Abnormality
Emergency
which
Impossible
Operation is
Action
When a No. 1
Compressor Failure
Occurs
When No. 2
Compressor Failure
Occurs
Trouble codes other than
those at left.
Emergency Operation only with the
No. 2 Compressor
❇
After the retry operation, even if
there is a diff
detected
erent abnormality
within <Inverter
code
at left, press the
Abnormality>
and after resetting, start
button
by emergency operation.
the unit
[Example]
4250 Reset Retry 4240
Reset Emergency
operation
Emergency Operation only with the
No. 1 Compressor
Overcurrent protection
400
500
No. 1 Compressor Failure
48 %
65 %
No. 2 Compressor Failure
65 %
65 %
(15) Emergency response operating mode
The emergency operation mode is a mode in which the unit is run in an emergency to respond to the trouble when the
compressors (No . 1, No. 2) break do wn, making it possib le to carr y out a abnor mality reset using the remote control.
1) Starting the Emergency Operation Mode
1 Trouble occurs (Display the abnormality code root and abnormality code on the remote control).
2 Carry out trouble reset with the remote control.
3
If the abnormality indicted in 1 above is of the kind that permits emergency operation (see the table below),
initiate a retry operation.
If the trouble indicated in 1 above is of the kind where emergency operation is impossible (see the table below),
restart operation after carrying out the previous abnormality reset (without entering the emergency operation
mode).
4 If the same abnormality is detected again during the retry operation in 3 above, carry out trouble reset once
more with the remote control, then try emergency operation starting corresponding to the contents of the
abnormality
Table Emergency Operation Mode Patterns and Abnormality Codes for which Emergency Operation is Possible or Impossible
set
on
Serial transmission trouble
0403
VDC sensor/circuit trouble
4200
Bus voltage trouble
4220
Radiator panel overheat
protection
4230
Overload protection
4240
4250
IPM Alarm output/
Bus voltage trouble/
Over Current Protection
Cooling fan trouble
4260
Thermal sensor trouble
(Radiator panel)
5110
IAC sensor/circuit trouble
5301