background image

12

GB

D

F

I

NL

E

SW

P

9.4. Location of wiring connections

Using the conduit mounting plates
Conduit mounting plates are supplied in three sizes (ø27, ø34, ø40). Choose
the size of mounting plate that matches the outer diameter of the conduit being
used.

9.3. Address settings

Outdoor unit address settings

When controlling a group, the address must be set for each outdoor unit.

During address setting, set all the dip switches SW1 (3 - 6) on the board to
<when shipped from factory: all OFF>. (Address setting is not necessary for
1:1 or Free multi-component systems.)

Settings using SW1 are given below.

Please set the mutually different address, and prevent the start up simultane-
ously. (In case of connecting with PEH-P400, 500)

10. Test  run

10.1. Test run

The test run can be carried out either from the outdoor unit or the indoor unit.

1. Checklist

After the installation, piping setup, and wiring of the indoor and outdoor units is
complete, check that refrigerant is not leaking, the power and control wires are
not loose, and the poles are not reversed. (When connecting model PEH-(R)P-
MYA in particular, check that there is current in the separate power supply
cable for the indoor unit.)

Use a 500 V insulation resistance tester to make sure that the resistance be-
tween the power terminal and the ground is 1.0 M

 or more. If it is less than

1.0 M

, do not operate the unit. * Absolutely do not touch the tester to indoor/

outdoor connection terminals S1, S2, and S3. An accident could occur.

Make sure there is no malfunction in the outdoor unit. (If there is a malfunction,
you can diagnose it using LED1 on the board.)

Check that the ball valve is fully open on both the liquid and gas ends.

Check the electrical power phase. If the phase is reversed, the fan may rotate
in the wrong direction or stop, or unusual sounds may be produced.

Starting at least 12 hours before the test run, send current through the
crankcase heater. (If the current is running for a shorter period of time,
damage to the compressor could result.)

After the above checks are complete, carry out the test run as indicated in the
following outline.

2. Starting and finishing the test run

Procedure from the indoor unit: carry out the test run as in the manual provided
with the indoor unit.

Procedure from the outdoor unit: start and stop the test run and set test run
mode (cooling/heating) using the SW4 dip switches on the board.

1

Set test run mode (cooling/heating) using SW 4-2.

2

The test run will begin when SW 4-1 is turned ON, according to the mode
selected by SW 4-2.

3

The test run is stopped when SW 4-1 is turned OFF.

Note:
Test run mode cannot be stopped during operation by using SW 4-2. (If the
operation mode is to be changed, first stop it using SW 4-1, then after chang-
ing the operation mode, start the test run again using SW 4-1.)

If the 2-hour timer is set, the test run will stop automatically after 2 hours.

During the test run, the room temperature display on the indoor unit will indi-
cate the temperature of the indoor unit piping.

When you operate the test run from OC1, all trial runs are completed by OC1

→ 

IC1 

→ 

MA 

→ 

IC1 

→ 

OC2.

cooling

run

<SW4>

heating

ON

1
2

stop

OFF

PEH-P400, 500

(IC1)

MA

OC1

OC2

SW1 function

switching

2 Error history  clear

Operation by switch manipulation

Clear

Outdoor unit address

Settings 0 - 15

OFF

ON

1

2

3

4

5

6

ON

OFF

(SW1)

Ordinary

 [Fig. 9.3.1] (P.5)

Model

1

3 Refrigerant system

address setting

4

5

6

9.5. Examples of refrigerant system address

setting

Ex.

1

2

* Set the refrigerant system address of one outdoor unit to 00 for the power supply

to the remote controller.
(The refrigerant system address is set to 00 when shipped from the factory.)
Do not duplicate the refrigerant system address settings within the same system.

Indoor unit

PEH-RP200, 250MYA

PEH-P400,

500MYA

Outdoor unit

No.1

No.2

Outdoor unit refrigerant

system address

00

00

01~15

Remote controller

power supply unit

9.6. Capacity control setting method (PEH-

P400, 500MYA only)

With the PEH-P400, 500MYA which has two outdoor units, the capacity can be
controlled to 0%, 50% or 100%.
This is set by setting the outdoor unit side dip switches as shown in the table below
before turning the power on.

DipSW5-1

No.1 side outdoor unit

OFF

No.2 side outdoor unit

ON

 [Fig. 9.4.1] (P.5)

A

When installing conduct from bottom panel

B

When installing conduct from front panel

C

Mounting plate (attached)

D

Knock-out hole

Remote controller communication – reception error

Remote controller  board error

Remote controller communication – transmission error

Remote controller communication – reception error

Remote controller communication – transmission error
Communication between indoor and outdoor units – reception error

Communication between indoor and outdoor units – transmission error

Communication between indoor and outdoor units – reception error

Communication between indoor and outdoor units – transmission error

Indoor/outdoor connection wiring error, indoor unit overload (5 units or more)

Indoor/outdoor connection wiring error (interference, loose)

Excessive time in use

Serial communication error

Error details

Problem location

Remote Controller

Remote Controller

Remote Controller

Indoor unit

Indoor unit

Indoor unit

Indoor unit

Outdoor unit

Outdoor unit

Outdoor unit

Outdoor unit

Outdoor unit

Outdoor unit

10.2. How to handle problems with the test run

Error code list: details

MELANS display

6831,6834

6201,6202

6832,6833

6831,6834

6832,6833
6740,6843

6841,6842

6840,6843

6841,6842

6844

6845

6846

0403

Remote controller

display

E0

E1, E2

E3

E4
E5

E6

E7

E8

E9

EA

EB

EC

ED

Summary of Contents for 250MYA

Page 1: ... uso seguro y correcto lea detalladamente este manual de instalación antes de montar la unidad de aire acondicionado MANUALE DI INSTALLAZIONE Per un uso sicuro e corretto leggere attentamente questo manuale di installazione prima di installare il condizionatore d aria INSTALLATIEHANDLEIDING Voor een veilig en juist gebruik moet u deze installatiehandleiding grondig doorlezen voordat u de aircondit...

Page 2: ...red at the site D Must be open E Wall height H F No restrictions on wall height L1 450 L2 250 PUH P200 250 7 7 2 H L H L L PUH P200 250 L 50 m H 40 m L Ra Rb 70 m L Ra L Rb 50 m Ra Rb 8 m H 40 m h 1 m 1 Single 2 Twin H h L R a R b PUH P200 250 Fig 7 2 1 A mm Å Outdoor unit ı Gas pipe size Ç Liquid pipe size PUH P200 ø25 4 ø12 7 PUH P250 ø28 58 ø12 7 B mm Î Indoor unit ı Gas pipe size Ç Liquid pipe...

Page 3: ...ly open state A Nitrogen gas B To indoor unit C System analyzer D Lo Knob E Hi Knob F Stop valve G Liquid pipe H Gas pipe I Outdoor unit J Service port B Ball valve liquid side Fig 8 4 4 Fig 8 4 3 Fig 8 4 2 C A B D E Fig 8 4 1 B A D C E E E D A B D F G B D Floor fireproofing E I B C Outer wall exposed A B A Inner wall concealed A B D C B Outer wall F H D B G E Roof pipe shaft I A J 1m 1m F Penetra...

Page 4: ...ecting with PEH P400 500 2 With heater B C D PUH P200 250 E E A B C A B C A A B C PUH P200 250 F 0 D A B C PEH P400 500 PUH P200 250 F 1 3 Grouping 16 outdoor units A D E E E E PUH P200 250 F 0 PUH P200 250 F 14 PUH P200 250 F 15 L1 L2 L3 N S1 S2 S3 S1S2 S3 L1 L2 L3 N S1 S2 S3 S1S2 S3 L1 L2 L3 N S1 S2 S3 S1S2 S3 S1S2 S3 B C A B C B C A 5 Grouping 16 outdoor units Connecting with PEH P400 500 A B C...

Page 5: ...N 1 2 3 4 5 6 7 OFF ON 1 2 3 4 5 6 8 OFF ON 1 2 3 4 5 6 9 OFF ON 1 2 3 4 5 6 10 OFF ON 1 2 3 4 5 6 11 OFF ON 1 2 3 4 5 6 12 OFF ON 1 2 3 4 5 6 13 OFF ON 1 2 3 4 5 6 14 OFF ON 1 2 3 4 5 6 15 ø40 ø27 ø27 ø34 ø34 ø38 1 C A B D Fig 9 4 1 9 4 A When installing conduct from bottom panel B When installing conduct from front panel C Mounting plate attached D Knock out hole 9 ...

Page 6: ...t the safety limit from being exceeded If the refrigerant leak and cause the safety limit to be exceeded hazards due to lack of oxygen in the room could result When moving and reinstalling the air conditioner consult the dealer or an authorized technician If the air conditioner is installed improperly water leakage electric shock or fire may result After completing installation work make sure that...

Page 7: ...ombine indoor units within the capacity of the outdoor unit Use ester oil ether oil or alkylbenzene small amount as the refrigerator oil to coat flares and flange connections The refrigerator oil will degrade if it is mixed with a large amount of mineral oil Use liquid refrigerant to fill the system If gas refrigerant is used to seal the system the composition of the refriger ant in the cylinder w...

Page 8: ...transmitted to the installation section and noise and vibration may be generated from the floor and walls depending on the installation con ditions Therefore provide ample vibrationproofing cushion pads cushion frame etc Be sure that the corners are firmly seated If the corners are not firmly seated the installation feet may be bent Warning Be sure to install unit in a place strong enough to withs...

Page 9: ...ing with PEH P400 500 Î Indoor unit 2 Twin 3 Triple 4 Four Caution Total bends are 15 units and max bends are 8 units within L R R R R Ra L R R R R Rb L R R R R Rc and L R R R R Rd 25 25 25 25 50 50 33 33 33 25 25 50 20 40 40 Model Additional refrigerant charge 8 Additional refrigerant charge 8 1 Additional refrigerant charge L Main section actual length Ra Rb Rc Rd Join section actual length The ...

Page 10: ...ncrease Turn the flare nut beyond this point by the angle shown in the table above Caution Always remove the connecting pipe from the ball valve and braze it out side the unit Brazing the connecting pipe while it is installed will heat the ball valve and cause trouble or gas leakage The piping etc inside the unit may also be burned Use ester oil ether oil or alkylbenzene small amount as the refrig...

Page 11: ... and connect it correctly Secure it so that the cable applies no external pressure to the terminal connection If the connection is faulty or the cable is not fully secured overheating or fire could result Caution Depending on the location of the unit a current leakage breaker may be required If a current leakage breaker is not installed electric shock could result Do not use breakers or fuses with...

Page 12: ...e operation mode is to be changed first stop it using SW 4 1 then after chang ing the operation mode start the test run again using SW 4 1 If the 2 hour timer is set the test run will stop automatically after 2 hours During the test run the room temperature display on the indoor unit will indi cate the temperature of the indoor unit piping When you operate the test run from OC1 all trial runs are ...

Page 13: ...h on the outdoor unit board the segments light up to indicate the running condition of the unit and the particulars of the check code SW2 setting 123456 000000 011110 010110 110110 011100 111100 Item Operation mode relay output Outdoor unit control condition Indoor unit control condition IC1 IC2 Indoor unit control condition IC3 IC4 Error code history 1 Error code history 2 Display contents tens p...

Page 14: ...he basis of time or piping temperature During defrosting the fan will stop When the supplementary electric heater is ON the fan will run for 1 minute after opera tion stops in order to expel excess hot air during heating only After the switch is turned to ON or until the piping temperature reaches 35 C there will be 5 minutes of light air operation After that there will be 2 minutes of low air ope...

Page 15: ... The product at hand is based on the following EU regulations Low Voltage Directive 73 23 EEC Electromagnetic Compatibility Directive 89 336 EEC This product is designed and intended for use in the residential commer cial and light industrial environment HEAD OFFICE MITSUBISHI DENKI BLDG 2 2 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN ...

Reviews: