background image

6

3. Transporting the unit

3.3. Precautions when lifting the unit (Fig. 3-3)

• When hang-lifting the unit, pass the sling or rope through the square-shaped holes

(there are 4) at the base. The rope must go up along the unit to the top as shown in
the picture. Please put small cushions between ropes and the unit (where the ropes
touch the unit) to protect the unit (plastic part) from any damages. (The rope can
cause scratches or dents to the unit.)

• Make sure that the angles between ropes (at the top) are less that 40 degrees.
• Always use 2 ropes to lift up the unit. Each rope must be at least 7 metres long and

must be able to support the weight of the unit.

 Caution:

Precautions When Transporting
• Units weighing 20 kg or more shall not be lifted by one person.
• Never touch the finned surface of the heat exchanger with your bare hands.

This area can cause cuts or damage.

• Never allow children to play with the plastic bag used for covering the unit.

Asphyxiation could occur. Always cut up the bag before disposing.

• Always use the designated spaces provided at the base of the unit when

lifting the unit. Make sure that four support points are always used. The unit
will be unstable and tip over or be dropped if lifted or transported using less
than four support points.

Fig. 3-3

4. Installing the outdoor unit

4.1. Positioning the anchor bolts

4.1.1. When installing a single outdoor unit (Fig. 4-1)

4.1.2. When installing multiple outdoor unit

• When installing in groups, always provide 90 mm of space between units.

4.2. Requests when installing the units (Fig. 4-2)

• Do not block the air passageways for the unit. If the air passageways are blocked,

trouble could occur in the operation of the unit.

 Warning:

• Always make certain that the surface onto which the unit is going to be in-

stalled has sufficient strength. If the surface is not strong enough, the unit
could fall over and cause damage or injury.

• Make sure that the unit is installed so that it will be able to withstand earth-

quakes and strong winds. Damage or injury could occur if the unit tips over
due to an earthquake or strong wind.

• Be sure to install the unit in a sturdy, level surface to prevent rattling noises during

operation.

<Foundation specifications>

Foundation bolt

M10 (J type)

Thickness of concrete

120 mm

Length of bolt

70 mm

Weight-bearing capacity

320 kg

• Make sure that the length of the foundation bolt is within 40 mm of the bottom

surface of the base.

• Secure the base of the unit firmly with four-M10 foundation bolts in sturdy locations.

* Procure the anchor bolts, nuts and washers locally.

4.3. Anchoring (Fig. 4-3)

• In order to enable the unit to withstand strong winds and earthquakes, make sure

that the anchor bolts are installed as shown in the illustration.

• Provide a strong foundation of concrete or angle iron.
• With some types of installation, vibration will be conveyed along the base to floors

and walls where it could create noise. In such locations, take measures to prevent
vibration (such as using anti-vibration pads or suspension mounting for the unit).

When performing the foundation work make sure that the floor surface has sufficient
strength and carefully route piping and wiring in consideration of water drainage that
will be required when the unit is operated.

Fig. 4-1

Fig. 4-2

Fig. 4-3

Prohibited installation

560   5

560   5

560   5

560   5

736   2

736   2

1

2

1

1

1

1

Outdoor unit

2

Service surface

560    5

700-796

736   2

2

1

3

1

2

3

1

Make sure there is
sufficient depth.

2

Installation base

3

Foundation

1

Receiving the corner section.

2

Make sure that the corner section is securely received. If the corner section is not securely
received, the anchoring points could bend.

3

Procure the M10 anchor bolts locally.

(mm)

(mm)

Max. 40°

Min. 90

Min. 90

Max. 40

4.1.1.

4.1.2.

Summary of Contents for 250 YHA-A

Page 1: ...English INSTALLATION MANUAL For safe and correct use please read this installation manual thoroughly before installing the air conditioner unit Air Conditioners PUHZ RP200 250 YHA A FOR INSTALLER ...

Page 2: ... it with any other refrig erant and do not allow air to remain in the lines Air enclosed in the lines can cause pressure peaks resulting in a rupture and other hazards Use only accessories authorized by Mitsubishi Electric and ask a dealer or an authorized technician to install them If accessories are incorrectly in stalled water leakage electric shock or fire may result Do not alter the unit Cons...

Page 3: ... in the refrigeration oil oil deterioration may result Do not use refrigerant other than R410A refrigerant If another refrigerant is used the chlorine will cause the oil to deteriorate Use the following tools specifically designed for use with R410A refrigerant The following tools are necessary to use R410A refrigerant Contact your nearest dealer for any questions Tools for R410A Gauge manifold Fl...

Page 4: ...e overall height of the unit add the dimen sion shown as h in the drawing on the left to L1 and L2 on Table 2 Table 2 mm L1 L2 450 100 2 4 2 When installing multiple outdoor units Fig 2 8 When installing multiple units make sure to take into consideration factors such as providing enough space for people to pass through ample space between blocks of units and sufficient space for air flow as shown...

Page 5: ...openings at the base of the unit Note 1 Always use care when transporting a unit by forklift on rainy days as slip page can occur 2 Never use dangerous sudden movements such as accelerating or applying the brakes suddenly or turning the steering wheel quickly when transporting the unit by forklift 3 2 Transporting by pallet truck Fig 3 2 When using a pallet truck to transport the unit insert the f...

Page 6: ... stalled has sufficient strength If the surface is not strong enough the unit could fall over and cause damage or injury Make sure that the unit is installed so that it will be able to withstand earth quakes and strong winds Damage or injury could occur if the unit tips over due to an earthquake or strong wind Be sure to install the unit in a sturdy level surface to prevent rattling noises during ...

Page 7: ...ne foam insu lation materials specific gravity of 0 03 thickness of 9 mm or more Apply thin layer of refrigerant oil to pipe and joint seating surface before tightening flare nut A Use two wrenches to tighten piping connections B Use leak detector or soapy water to check for gas leaks after connections are com pleted Apply refrigerating machine oil over the entire flare seat surface C Do not apply...

Page 8: ...air from the refrigerant lines After the valve work is completed tighten the valve caps to the correct torque Valve size Tightening torque N m kgf cm Valve cap Service port cap 3 8 ø9 52 22 28 220 280 12 16 1 2 ø12 7 25 31 250 310 120 160 1 ø25 4 36 44 360 440 11 5 13 9 115 139 Failure to replace and tighten the caps may result in refrigerant leakage In addition do not damage the insides of the va...

Page 9: ... less 41 50 m and less 51 60 m and less 61 70 m and less 71 120 m and less 0 9 kg 1 8 kg 2 7 kg 3 6 kg 1 2 kg 2 4 kg 3 6 kg 4 8 kg Outdoor unit RP200 RP250 At time of shipping kg 10 5 10 5 No additional charge necessary Calculate the amount of additional refrigerant charge using formula provided below Main piping Liquid line size ø9 52 overall length 0 09 Gasline ø28 58 m 0 09 kg m Branch piping L...

Page 10: ...ner from the pipes The existing piping can be reused After flaring the pipes again connect the new air conditioner The existing pipes cannot be reused Use new pipes 5 Installing the refrigerant piping 5 8 For twin triple quadruple combination Fig 5 8 When this unit is used as a FREE COMPO MULTI unit install the refrigerant piping with the restrictions indicated in the drawing on the left In additi...

Page 11: ...ting cords shall not be lighter than polychloroprene sheathed flexible cord Design 245 IEC 57 3 Use an earth wire which is longer than the other cords so that it will not become disconnected when tension is applied The earth wire should also be thicker than the power supply cord so that it can stand any surge of electricity when trouble occurs 7 2 Field electrical wiring If the wiring connecting t...

Page 12: ...ended period the insulation resistance will drop below 1 MΩ due to refrigerant accumulat ing in the compressor This is not a malfunction Perform the following procedures 1 Remove the wires from the compressor and measure the insulation resistance of the compressor 2 If the insulation resistance is below 1 MΩ the compressor is faulty or the resist ance dropped due the accumulation of refrigerant in...

Page 13: ...W4 2 ON After performing the test run set SW4 1 to OFF After power is supplied a small clicking noise may be heard from the inside of the outdoor unit The electronic expansion valve is opening and closing The unit is not faulty A few seconds after the compressor starts a clanging noise may be heard from the inside of the outdoor unit The noise is coming from the check valve due to the small differ...

Page 14: ...ltaneous twin Refrigerant address 01 G Simultaneous triple Refrigerant address 02 ON OFF 3 4 5 6 E SW 1 3 6 ON OFF 3 4 5 6 F SW 1 3 6 ON OFF 3 4 5 6 G SW 1 3 6 Operation according to switch setting ON OFF Start Normal Clear Normal Settings for outdoor unit ad dresses 0 to 15 SW1 Function table SW1 Function 1 Compulsory de frosting 2 Error history clear 3 4 5 6 ON 1 2 3 4 5 6 OFF TB4 TB5 TB1 TB4 TB...

Page 15: ......

Page 16: ...ase be sure to put the contact address telephone number on this manual before handing it to the customer HEAD OFFICE TOKYO BLDG 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN Printed in Japan BG79U638H03 ...

Reviews: