15
(2) When connecting the terminating resistor and FG cable
When connecting the terminating resistors to the GOT, be sure to
connect the terminating resistors (with the supplied plate type solderless
terminal) at the position as shown below.
When connecting the FG cable, strip the wire sheath of the FG cable
(2mm
2
) off for 10mm (0.39 inch) and insert it into the terminal block
socket.
POINT
• Tighten the terminal block wiring screws with the tightening torque of 0.5 to 0.6
N
•
m.
• Tighten terminal block mounting screws with the tightening torque of 0.7 to 0.8
N
•
m.
• The terminating resistors supplied with the master module or the CC-Link com-
munication unit must be connected to the PLC module or GOT at both ends of
the data link. (Connect them across DA-DB.)
• Connect the shield wire of the CC-Link dedicated cable to SLD of each module.
Since SLD is connected to FG internally, always ground the FG terminal and
FG1 terminal to the protective ground conductor.
• The FG terminal of the GOT power supply and the FG terminal of the CC-Link
Communication unit must be connected separately.
• When using the plate type solderless terminal, be sure to insert the terminal in
the horizontal direction toward the terminal block.
The solderless terminal may come off when it is inserted in the vertical direc-
tion.
10mm
(0.39inch)
FG SLD
DG DB
DA
Terminating resistor
(with plate type
solderless terminal)
Power supply cable
Conductor plate
Braid
shield