2
2. SPECIFICATIONS
2.1 Performance Specifications
The following is the performance specification of CC-Link communication unit.
The general specification of the CC-Link communication unit are the same as
those of the GOT.
For the general specifications of the GOT refer to the User's Manual for the GOT
used.
*
1
*1 When installing an extension unit on the CC-Link communication
unit, limit the maximum operating ambient temperature by
subtracting 5 degrees from operating ambient temperature of the
general specifications.
*2 Each of the I/O signals (RX, RY) occupies 16 points of a system
area within device points.
For more details on the I/O signals, refer to Section 3.1.
Item
Specifications
CC-Link station type
Intelligent device station
Number of occupied stations
May be selected between 1 and 4.
Maximum number of link
points per system
Ver.2
mode
Remote I/O(RX, RY)*
2
8192 points
Remote register(RWw)
2048 points
Remote register(RWr)
2048 points
Ver.1
mode
Remote I/O(RX, RY)*
2
2048 points
Remote register(RWw)
256 points
Remote register(RWr)
256 points
Number of link points per station
Refer to *3
Number of link points per number of
occupied stations
Refer to *4
Transmission speed
156kbps/625kbps/2.5Mbps/5Mbps/10Mbps
Max. transmission distance
Depends on the transmission speed.
Max. number of modules connected
26
The max. number of modules connected depends on the
configuration of the CC-Link system to be used.
For more details on the max. number of modules
connected, refer to the CC-Link System Master-Local
Module User’s Manual.
Connection cable
CC-Link dedicated cable
Internal current consumption
(5VDC)
0.56A
Weight
0.18kg (0.40Ib)