MITSUBISHI ELECTRIC 1100B SERIES UPS
1100B SERIES UPS
OWNERS / TECHNICAL MANUAL
Page Number:
1-8
This UPS does not include an AC input circuit breaker (MCCB) to protect the bypass
and main input circuit. The AC input circuit breaker (MCCB) is to be field supplied
and installed. The recommended circuit breaker (MCCB) specifications are as
follows:
Table 2
Rating of AC Input Circuit Breaker
Capacity (kVA)
Input Voltage (VAC)
Maximum AC Input
Rating (AAC)
Recommended
Breaker (A)
10
208
30
40
20
208
60
80
30
208
90
110
40
208
120
150
50
208
150
225
60
208
180
225
70
208
210
275
80
208
240
300
AC input and AC output over current protection and disconnect devices shall be field supplied
and installed. DC output over current protection and disconnect devices shall be field supplied
and installed.
This UPS functions with lead acid batteries. If a
▲
is seen, review the
supplemental materials for more information about the stored energy system used.