MITSUBISHI ELECTRIC 1100B SERIES UPS
1100B SERIES UPS
OWNERS / TECHNICAL MANUAL
Page Number:
1-18
Table 5
Detail of Specifications
▲
▲ For other stored energy systems, refer to the supplement.
Type
UP1133B-
A103SU-2
UP1133B-
A203SU-2
UP1133B-
A303SU-2
UP1133B-
A403SU-2
UP1133B-
A503SU-2
UP1133B-
A603SU-2
UP1133B-
A703SU-2
UP1133B-
A803SU-2
Rated Output kVA
10
20
30
40
50
60
70
80
Rated Output kW
9
18
27
36
45
54
63
72
AC INPUT CHARACTERISTICS
Configuration
3-phase, 3-wire, plus ground
Voltage
120/208 V +15% ~ -30%
Frequency
60 Hz +/- 10%
Reflected Current THD
4% typical at 100% load; 7% typical at 50% load
BYPASS INPUT
Configuration
3-phase, 4-wire, plus ground
Voltage
120/208 V +10%
Frequency
60 Hz +/- 10%
AC OUTPUT
Configuration
3-phase, 4-wire
Voltage
120/208 V
Voltage Stability
+/-1%
Frequency
60 Hz
Frequency Stability
+/-0.01% in free running mode
Power Factor
0.9 nominal
Power Factor range
0.9 ~ 1.0 lagging (within output kW rating)
Voltage THD
2% typical THD at 100% linear load
5% typical THD at 100% non-linear load
Transient Response
+/-3% typical at 100% load step
+/-1% typical at loss/return of AC power
+/-5% typical at load transfer to/from static bypass
Transient Recovery
16.7 ms
Voltage Unbalance
+/-2% typical at 100% unbalanced load
Voltage Phase Angle
Displacement
+/-1deg. typical at 100% load
Inverter Overload
105% to 125% for 60 seconds; 126% to 150% for 30 seconds
System Overload
1000% for 1 cycle (with bypass available)
Crest Factor
Capabilities
2.5 : 1
ENVIRONMENTAL
Cooling
Forced Air
Operating Temperature
41 deg F ~ 95 deg F (5 deg C ~ 35 deg C).
Recommended 68 deg F ~ 77 deg F (20 deg C ~ 25 deg C)
Relative Humidity
5% ~ 95% Non-Condensing
Altitude
Will vary with model
Location
Temperature-controlled, indoor area free of conductive contaminants
Paint Color
Munsell N1.5 (Black)