MITSUBISHI ELECTRIC 1100B SERIES UPS
1100B SERIES UPS
OWNERS / TECHNICAL MANUAL
Page Number:
6-4
Code
indication
(Note 2)
Status
Message
Meaning
Guidance
Audible
Alarm
External
relay
contact
(Note 1)
UF323
UPS CONTROL
CIRCUIT ERROR
Major communication error during
parallel operation.
CALL
SERVICE
ENGINEER
Intermittent
sound
Minor
UF340
MODULE MINOR
FAULT
A power converter module has
detected major fault condition.
CALL
SERVICE
ENGINEER
Intermittent
sound
Minor
UF341
MODULE1 MAJOR
FAULT
Power converter module #1 has
detected major fault condition.
CALL
SERVICE
ENGINEER
Intermittent
sound
Minor
UF342
MODULE2 MAJOR
FAULT
Power converter module #2 has
detected major fault condition.
CALL
SERVICE
ENGINEER
Intermittent
sound
Minor
UF343
MODULE3 MAJOR
FAULT
Power converter module #3 has
detected major fault condition.
CALL
SERVICE
ENGINEER
Intermittent
sound
Minor
UF344
MODULE4 MAJOR
FAULT
Power converter module #4 has
detected major fault condition.
CALL
SERVICE
ENGINEER
Intermittent
sound
Minor
UF345
MODULE5 MAJOR
FAULT
Power converter module #5 has
detected major fault condition.
CALL
SERVICE
ENGINEER
Intermittent
sound
Minor
UF349
MODULE MAJOR
FAULT
All Power converter modules have
detected major fault condition.
CALL
SERVICE
ENGINEER
Continuous
sound
Major
UF351
CONTROL POWER
SUPPLY
ABNORMAL
Control power supply voltage is
below the specified level. (Bypass)
CALL
SERVICE
ENGINEER
Intermittent
sound
Minor
UF352
CONTROL POWER
SUPPLY
ABNORMAL
Control power supply voltage is
below the specified level. (Output)
CALL
SERVICE
ENGINEER
Intermittent
sound
Minor
UF353
CONTROL POWER
SUPPLY
ABNORMAL
External IO control power supply
voltage is below the specified level.
CALL
SERVICE
ENGINEER
Intermittent
sound
Minor
UF372
UPS CONTROL
CIRCUIT ERROR
Unable to synchronize the inverter
output and the bypass voltage.
CALL
SERVICE
ENGINEER
Intermittent
sound
Minor
UF376
UPS CONTROL
CIRCUIT ERROR
Logic signal abnormal (Supply ON).
CALL
SERVICE
ENGINEER
Intermittent
sound
Minor
UF377
UPS CONTROL
CIRCUIT ERROR
Logic signal abnormal (Supply
OFF).
CALL
SERVICE
ENGINEER
Intermittent
sound
Minor
UF401
52S ABNORMAL
Error to close the contactor 52S.
CALL
SERVICE
ENGINEER
Continuous
sound
Major
UF402
52S ABNORMAL
Error to open the contactor 52S.
CALL
SERVICE
ENGINEER
Continuous
sound
Major
UF452
CB3 ABNORMAL
Contactor CB3 is not working
properly.
CALL
SERVICE
ENGINEER
Intermittent
sound
Minor