41
SRK-GZ
Is discharge pipe (Comp. dome)
thermistor resistance value good?
Is sufficient quantity of refrigerant
circulated?
Defective inverter
YES
YES
NO
NO
YES
NO
Gas shortage
Connector connection check, resistance
value check, replacement of discharge pipe
(Comp. dome) thermistor
Does trouble persist after
charging gas?
Clogged capillary tube,
etc.
Outdoor unit error
[Broken power transistor
broken compressor wire]
Current safe stop
[Overload operation, compressor
lock, overcharge]
Compressor overheat
[Gas shortage, defective discharge
pipe (Comp. dome) thermistor]
Secure space for suction and blow
out.
Discharge refrigerant.
Is refrigerant charge quantity adequate?
Is outdoor ventilation condition good?
Inspect compressor.
Defective inverter
YES
YES
NO
NO
YES
Is output voltage applied to all 3
phases of power transistor?
Defective inverter
Is compressor wiring connected
securely?
Connect securely.
Inspect compressor.
YES
YES
NO
NO