The commands should be the same for all of the five GPO cues you create. The
command should be “Pulse Up”, and the duration 500 milliseconds. You will change the
output according to which function the cue performs, as shown in Figure 6-5.
GPO
Output
Function
1 Dimmer Mid
2 Dimmer Down
3 Dimmer Up
GPO 4 is not used by the BP1
5 Screen Lights On
6 Screen Lights Off
GPO 7 and 8 are not used by the BP1
Figure 6-5
Configuring the ICMP-X GPI Cues
6. Next, create the two GPI cues that the ICMP-X receives from the BP1. These handle
the fire alarm functions. They enable the show to be stopped or paused automatically
when the fire alarm activation signal is sent, and then restarted when the “all clear” signal
is sent from the fire alarm system, via the BP1.
In the cue editor, go to the Input Cues tab, and then press Add.
Figure 6-6