background image

8

– English

English

TABLE 1 – Technical specifications of electric cables

(see also paragraph 4.2)

Connection

Cable type

Maximum admissible len

A

- FLASHING LIGHT cable

Cable 2 x 1.0 mm

2

10 m 

(note 2)

B

- POWER SUPPLY cable

Cable 3 x 1.5 mm

2

(note 1)

30 m

D

- BUS cable

Cable 2 x 0.5 mm

2

20 m 

(note 3)

Note 

– The cables required for the set-up of the system (not included in the pack) may vary according to the quantity and type of

components envisaged for the system.

Note 1

– If the power cable supplied is not long enough, replace with a cable of this type. This task must be performed by skilled

and qualified personnel: Refer to the section “

Tasks reserved for qualified technicians

”.

Note 2

– If a greater length is required use a cable with diameter 2 x 1.5 mm

2

.

Note 3

– If a greater length is required use a cable with diameter 2 x 1.0 mm

2

.

CAUTION! 

– The cables used must be suited to the installation environment; for example a cable type H07RN-F for out-

door environments is recommended.

4.1

.5 – 

Checking the tools required for work

Before starting installation, ensure that there is all equipment and materi-
als required for the work concerned (see example in 

fig. 6

); also ensure

that all items are in good condition and comply with local safety stan-
dards.

4.1

.6 – 

Preliminary set-up work

Dig the routes for the ducting used for electrical cables, or alternatively
external ducting can be laid, after which the pipelines can be embedded
in concrete and other preparation work for the installation can be com-
pleted to finalise the site ready for subsequent installation operations.

In particular, for digging the pit for anchoring the gearmotor to the
ground, proceed as follows:

01.

Dig the foundation pit in the gearmotor fixture point: refer to STEP 

3.2

Note

– The dimensions of the pit must be the same or greater than

those of the foundation plate.

02.

Lay the ducting used for electrical cables as shown in the figure
below.

CAUTION!

– In general, position the ends of the ducting used for

electrical cables in the vicinity of the points envisaged for fixture of
the various components.

Note:

The ducting serves to protect electrical cables and prevent acci-

dental damage in the event of impact.

4.2

– PREPARING THE ELECTRICAL CABLES 

When preparing the electrical cables required for your system, please
refer to 

fig. 7

and “

Table 1 – Technical characteristics of the electric

cables

”. In addition to this, you should always remember the following:

– In the “star” configuration, NONE of the individual cables linking up
any of the devices to the Control Unit may exceed 20 m in length.

– In the “chain” configuration”, the sum of the lengths of each cable
used to connect one device to the other and, last of all, to the Con-
trol Unit MUST NOT exceed 20 m. 

– If connecting other devices between the Control Unit and the flash-
ing lamp, use the same cable for these devices as was used for the
flashing lamp.

– All operations to lay the electric cables and connect them to the
various devices must be carried out during installation of the com-
ponents. 

7

A

B

C

C

C

C

C

Summary of Contents for Moovo LN4 Series

Page 1: ......

Page 2: ...unit 12 6 2 Installing and connecting flashing light mod MF 12 6 3 Installing and connecting photocells mod MP 14 Selecting the photocell pair operating mode 15 6 4 Installing and connecting keypad m...

Page 3: ...If this is the first time you are setting up an automation for sliding gates we recommend that you read this entire manual with care This is prefer able before any work without any hurry to start prac...

Page 4: ...trol unit can memorise up to 150 keys of MT4 transmitters up to 4 MK control keypads or alternatively up to 4 pairs of MP photocells set for the opening command only Connections of the various devices...

Page 5: ...f accidental impact Ensure that the selected surfaces for fixing the photocells are flat and enable correct alignment between photocells 3 2 CHECKING PRODUCT APPLICATION LIMITS To ascertain suitabilit...

Page 6: ...nals on the control unit mixed this configuration is a combination of the two configurations described above To select the most suitable connection configuration for the connection of all system devic...

Page 7: ...edded in concrete and other preparation work for the installation can be com pleted to finalise the site ready for subsequent installation operations In particular for digging the pit for anchoring th...

Page 8: ...fectly level use a spirit level 04 When the concrete is solid after a few days loosen and remove the upper nuts of the plate which are no longer required 05 Remove the gearmotor cover using a screwdri...

Page 9: ...t so move the bracket to this position and if necessary use a hacksaw to cut off the excess section of the rack leaving a free section of approx 5 cm IMPORTANT the rack must not protrude from the gate...

Page 10: ...NECTIONS OF SYSTEM DEVICES Install and connect the system devices with reference to the STEPS below and the example in fig 17 CAUTION Incorrect connections can cause faults or hazards therefore ensure...

Page 11: ...icates execution of each manoeuvre It is also con nected to the diagnostics system of the control unit and in the event of malfunctions signals the type of problem by means of a pre set sequence of fl...

Page 12: ...the cap of the flashing unit in its seat until the tabs click in place 21 20 22 08 Fig 23 Refit the transparent cover in its seat and turn clockwise taking care that the serrated section engages with...

Page 13: ...p by pushing down one side as shown in the figure 02 Fig 26 Using a screwdriver open and detach the base of the photocell 03 Fig 27 a Drill a hole on the pre cut section on the base for routing the co...

Page 14: ...oceed as follows 01 Open the cover of the photocell 02 In fig 31 locate the position in which the specific photocells are installed 03 In Table 2 select the required configuration and insert electric...

Page 15: ...ypad cover by pushing down one side as shown in the figure 02 Fig 33 Using a screwdriver open and detach the base of the keypad 03 Fig 34 a Drill a hole on the pre cut section on the base for routing...

Page 16: ...id the risk of leaks of harmful sub stances Battery disposal CAUTION Even if discharged the batteries can contain pollutant sub stances and therefore must NEVER be disposed of in common waste col lect...

Page 17: ...nnections refer also to the paragraph What to do if 41 L2 green led L1 red led Key P1 STEP 7 WARNINGS The PVC power supply cable supplied serves exclusively for automation operation and programming te...

Page 18: ...ing light 1 flash and the keypad 1 beep if fitted on the system 05 on the keypads Activate the keypads if fitted on the system by pressing any key on each one as required Successful learning is confir...

Page 19: ...ey for example Command 2 03 Press P1 on the Control unit the same number of times as the selected command number in the example 2 i e twice and check that the green led emits the same number of quick...

Page 20: ...press key T3 Leaf deceleration points press key T4 04 Lastly refer to Table 3 select the required value in correspondence with the selected function and on the transmitter press the key asso ciated w...

Page 21: ...s first then the red led illuminates after 5 seconds and then both to indicate that the Control unit has entered memory deletion mode Then release the key 02 With reference to Table 4 select the data...

Page 22: ...version of movement The automation does not respond to commands After a series of manoeuvres sent consecutively the automation is blocked The automation does not respond to commands The automation doe...

Page 23: ...rictly observed In the case of this product the cable supplied may need to be replaced with a protected electric line suited to the installation In this case use a power cable with the dimensions 3 x...

Page 24: ...ll devices used and the declaration of conformity compiled by the installer see section TECHNICAL DOCUMENTATION 2 Affix a dataplate on the door specifying at least the following data type of automatio...

Page 25: ......

Page 26: ...ered and sends the output signals Absorbed power 120mW in funzionamento 45mW in stand by Ambient operating temperature 20 50 C Use in acid saline or potentially No explosive atmospheres Assembly Verti...

Page 27: ......

Reviews: