12
6.0
Operating Instructions
Normal
All indicators are normally OFF except for the green A.C. ON light which illuminates steadily.
Alarm
Operate Alarm Initiating Devices to activate Indicating Appliances. Signals will sound,
common alarm will illuminate red.
Silencing of
Alarm
Press Signal Silence button momentarily to silence all audible signals.
Note:
The signal silencing function may be inhibited for up to one minute. The Signal
silence button will not operate until the inhibit period has expired.
Waterflow
Indicating appliances and other output circuits that are activated in response to an alarm
initiated by a designated Waterflow Zone cannot be silenced (manual or automatic).
Supervisory
Activation of any initiating devices for supervisory will sound the buzzer continuously. The
Common supervisory indicator will illuminate amber (steady). The Common Supervisory
indicator remains "ON" when the buzzer is silenced.
System
Reset
Press the Reset button momentarily to restore normal operation. All alarm indicators will
extinguish &
all latched functions are restored.
Trouble
Any system trouble will sound the buzzer intermittently and common Trouble indicator will
flash amber until the fault is corrected. Specific types of trouble will be indicated by the LCD
display by pressing the INFO button. Call for service.
Fire Drill
Press the Fire Drill button momentarily to sound all audible signals without initiating an
alarm. Press the button again for normal system operation.
Note:
Auxiliary relays will not
operate when Fire Drill is operated.
Lamp Test
Press the Lamp Test button momentarily to test all indicators except the CPU Fail LED. All
indicators should be lit and buzzer will sound. Holding down this button will display the
firmware version.
CPU Fail LED
Will illuminate amber for an onboard CPU error. In addition, the buzzer sounds steadily until
the fault is corrected.
To test the CPU Fail LED
1. Disconnect power from the RAM-300LCD.
2. Connect the power to the RAM-300LCD as described in section 4.0 on page 9.
If the CPU Fail LED is functioning properly, it will flash once when the RAM-300LCD
powers up.
Menu Button
Press the Menu button to access the associated FA-300 Series Fire Alarm Panel. The Menu
button operates as it does on the main FA-300 Series Fire Alarm Panel, refer to the fire
alarm manual for further explanation. Use the keypad arrow keys (2, 4, 6 and 8) to scroll
through the menu. Configuration of the fire alarm panel cannot be accessed from the RAM-
300LCD. The Menu button does not operate for the FX-350/351 Series Fire Alarm Panels.
Enter, Cancel
and Info
Buttons
The Enter and Cancel buttons are used to input and erase some data for the fire alarm panel
and the Info button is used to view the fire alarm panel logs. The Enter and Cancel buttons
do not operate for the FX-350/351 Series Fire Alarm Panels.
Keypad
The numbered keys and/or letter keys function as they do at the FA-300 Series Fire Alarm
Panel, refer to the fire alarm manual for further explanation. The keypad does not operate
for the FX-350/351 Series Fire Alarm Panels.
i
firealarmresources.com
Summary of Contents for RAM-300LCD Series
Page 2: ...firealarmresources com...