background image

15

Warranty and Warning Information

13.

Wireless Devices Placement Proximity.  

Moreover all wireless devices must be a minimum 

and maximum distance away from large metal objects, such as refrigerators.  You are required 
to consult the specific Mircom System manual and application guide for any maximum 
distances required between devices and suggested placement of wireless devices for optimal 
functioning.  

14.

Failure to Trigger Sensors.  

Moreover, Mircom Systems may fail to operate as intended if 

motion, heat, or smoke sensors are not triggered.  

a. Sensors in a fire system may fail to be triggered when the fire is in a chimney, walls, roof, 

or on the other side of closed doors.  Smoke and heat detectors may not detect smoke 
or heat from fires on another level of the residence or building.  In this situation the 
control panel may not alert occupants of a fire.  

b. Sensors in a nurse call system may fail to be triggered when movement is occurring 

outside of the motion sensors’ range. For example, if movement is occurring on the other 
side of closed doors or on another level of the residence or building the motion detector 
may not be triggered.  In this situation the central controller may not register an alarm 
signal.

15.

Interference with Audible Notification Appliances.  

Audible notification appliances may be 

interfered with by other noise sources such as stereos, radios, televisions, air conditioners, 
appliances, or passing traffic.  Audible notification appliances, however loud, may not be heard 
by a hearing-impaired person.

16.

Other Impairments.  

Alarm notification appliances such as sirens, bells, horns, or strobes 

may not warn or waken a sleeping occupant if there is an intervening wall or door.  It is less 
likely that the occupants will be alerted or awakened when notification appliances are located 
on a different level of the residence or premise.

17.

Software Malfunction.  

Most Mircom Systems contain software.  No warranties are provided 

as to the software components of any products or stand-alone software products within a 
Mircom System.  For a full statement of the warranties and exclusions and limitations of 
liability please refer to the company’s standard Terms and Conditions and Warranties.  

18.

Telephone Lines Malfunction.  

Telephone service can cause system failure where telephone 

lines are relied upon by a Mircom System. Alarms and information coming from a Mircom 
System may not be transmitted if a phone line is out of service or busy for a certain period of 
time. Alarms and information may not be transmitted where telephone lines have been 
compromised by criminal tampering, local construction, storms or earthquakes.

19.

Component Failure.

  Although every effort has been made to make this Mircom System as 

reliable as possible, the system may fail to function as intended due to the failure of a 
component.

20.

Integrated Products.  

Mircom System might not function as intended if it is connected to a 

non-Mircom product or to a Mircom product that is deemed non-compatible with a particular 
Mircom System.  A list of compatible products can be requested and obtained.

Warranty

Purchase of all Mircom products is governed by:

https://www.mircom.com/product-warranty

https://www.mircom.com/purchase-terms-and-conditions

https://www.mircom.com/software-license-terms-and-conditions

firealarmresources.com

Summary of Contents for RAM-300LCD Series

Page 1: ...AM 300LCD Series FA 300 SERIES Remote Annunciator SYSTEM RESET SIGNAL SILENCE FIRE DRILL BUZZER SILENCE LAMP TEST 4 1 7 2 5 8 0 3 6 9 ENTER MENU CANCEL INFO ABC DEF GHI JKL MNO PRS TUV WXY QZ A C ON A...

Page 2: ...firealarmresources com...

Page 3: ...otentiometer 7 3 3 DIP Switches 8 4 0 Wiring 9 5 0 Specifications Features 11 5 1 Enclosure 11 5 2 Electrical Specifications 11 5 3 Current Drain for Battery Calculations 11 5 4 Environmental Specific...

Page 4: ...2 Mechanical Installation 6 Figure 3 Annunciator Component Descriptions 7 Table 1 Jumpers 7 Table 2 RAM 300LCD Address DIP Switch Setup 8 Table 3 DIP switch SW31 settings 8 Table 4 Maximum Wiring Run...

Page 5: ...ional Setup section following This annunciator may be selected to operate as an ancillary device using DIP Switch SW31 6 to disable all buttons except Lamp Test Buzzer Silence Info and Arrow Buttons N...

Page 6: ...This enclosure may also be mounted to a 4 square electrical box There are two conduit areas provided at the bottom center of the enclosure With the dead front plate removed you may do the functional s...

Page 7: ...AL SILENCE FIRE DRILL BUZZER SILENCE LAMP TEST 1 4 7 2 5 8 0 3 6 9 ENTER MENU CANCEL INFO ABC DEF GHI JKL MNO PRS TUV WXY QZ A C ON ALARM SUPV TRBL CPU FAIL SYSTEM NORMAL 18 01 MON 2011 02 07 24V IN O...

Page 8: ...ON ON ON Note SW30 4 DIP switch is not used Note For the FX 350 351 Series Fire Alarm Panels if the number of annunciators programmed is 5 then the first five addresses 1 to 5 inclusive must be assign...

Page 9: ...ain for Battery Calculations on page 11 and calculate the Maximum current for all annunciators summed together Note All circuits are power limited and must use type FPL FPLR or FPLP Power Limited Cabl...

Page 10: ...m E O L resistor connected to the RS 485 positive and negative terminals 24V IN OUT S RS 485 IN OUT S R S 4 8 5 24V IN OUT S RS 485 IN OUT RAM 300LCD ADDRESS 1 RAM 300LCD ADDRESS 2 FA 300 FIRE ALARM P...

Page 11: ...5 3 Current Drain for Battery Calculations The maximum normal current drain will be during Lamp Test when all lamps are illuminated on one chassis at a time Thus the currents are Normal Standby 56 mA...

Page 12: ...ain for normal system operation Note Auxiliary relays will not operate when Fire Drill is operated Lamp Test Press the Lamp Test button momentarily to test all indicators except the CPU Fail LED All i...

Page 13: ...em a substitute for property owners renters or other occupants to act prudently to prevent or minimize the harmful effects of an emergency situation Building automation systems produced by the Mircom...

Page 14: ...ovide timely warning of fires caused by carelessness or safety hazards such as smoking in bed violent explosions escaping gas improper storage of flammable materials overloaded electrical circuits or...

Page 15: ...ication appliances such as sirens bells horns or strobes may not warn or waken a sleeping occupant if there is an intervening wall or door It is less likely that the occupants will be alerted or awake...

Page 16: ...5 Tel 905 660 4655 888 660 4655 Fax 905 660 4113 Mircom 2018 Printed in Canada Subject to changewithout priornotice www mircom com CANADA Main Office 25 Interchange Way Vaughan ON L4K 5W3 Tel 905 660...

Reviews: