background image

9

4.0   

Wiring

To wire the RAM-300LCD, you must first remove the dead front plate.  Wire from the last RAM-
300LCD to the next RAM-300LCD and so on; then from the first RAM-300LCD to the Fire
Alarm Panel.  There are only two connections to be made, one for power and the RS-485 loop.
Replace the dead front plate once all functional setup and wiring is complete.

The 

RS-485 Wiring

 to the RAM-300LCD is recommended to be 

Twisted Shielded Pair.

   The

wire gauge may be

22 AWG up to 2000 ft.

20 AWG up to 4000 ft.

The 24V DC field wiring needs to be of an appropriate gauge for the number of annunciators
and the total wiring run length. See Current Drain for Battery Calculations on page 11 and
calculate the 

Maximum

 current for all annunciators summed together.

Note:

All circuits are power limited and must use type FPL, FPLR or FPLP Power
Limited Cable.

Attention:

Accidentally connecting any of the 24V DC wires to the RS-485 wiring will

result in damage to the Annunciator and/or to the Fire Alarm Control Panel to

which it is connected.

Table 4  Maximum Wiring Run to Last Annunciator

Max for all 

Annunciators

Max Loop 

Resistance

18AWG

16AWG

14AWG

12AWG

Amperes

ft

m

ft

m

ft

m

ft

m

Ohms

0.12

1180

360

1850

567

3000

915

4250

1296

15

0.30

470

143

750

229

1200

366

1900

579

6

0.60

235

71

375

114

600

183

850

259

3

0.90

156

47

250

76

400

122

570

174

2

1.20

118

36

185

56

300

91

425

129

1.5

1.50

94

29

150

46

240

73

343

105

1.2

1.70

78

24

125

38

200

61

285

87

1.0

i

!

firealarmresources.com

Summary of Contents for RAM-300LCD Series

Page 1: ...AM 300LCD Series FA 300 SERIES Remote Annunciator SYSTEM RESET SIGNAL SILENCE FIRE DRILL BUZZER SILENCE LAMP TEST 4 1 7 2 5 8 0 3 6 9 ENTER MENU CANCEL INFO ABC DEF GHI JKL MNO PRS TUV WXY QZ A C ON A...

Page 2: ...firealarmresources com...

Page 3: ...otentiometer 7 3 3 DIP Switches 8 4 0 Wiring 9 5 0 Specifications Features 11 5 1 Enclosure 11 5 2 Electrical Specifications 11 5 3 Current Drain for Battery Calculations 11 5 4 Environmental Specific...

Page 4: ...2 Mechanical Installation 6 Figure 3 Annunciator Component Descriptions 7 Table 1 Jumpers 7 Table 2 RAM 300LCD Address DIP Switch Setup 8 Table 3 DIP switch SW31 settings 8 Table 4 Maximum Wiring Run...

Page 5: ...ional Setup section following This annunciator may be selected to operate as an ancillary device using DIP Switch SW31 6 to disable all buttons except Lamp Test Buzzer Silence Info and Arrow Buttons N...

Page 6: ...This enclosure may also be mounted to a 4 square electrical box There are two conduit areas provided at the bottom center of the enclosure With the dead front plate removed you may do the functional s...

Page 7: ...AL SILENCE FIRE DRILL BUZZER SILENCE LAMP TEST 1 4 7 2 5 8 0 3 6 9 ENTER MENU CANCEL INFO ABC DEF GHI JKL MNO PRS TUV WXY QZ A C ON ALARM SUPV TRBL CPU FAIL SYSTEM NORMAL 18 01 MON 2011 02 07 24V IN O...

Page 8: ...ON ON ON Note SW30 4 DIP switch is not used Note For the FX 350 351 Series Fire Alarm Panels if the number of annunciators programmed is 5 then the first five addresses 1 to 5 inclusive must be assign...

Page 9: ...ain for Battery Calculations on page 11 and calculate the Maximum current for all annunciators summed together Note All circuits are power limited and must use type FPL FPLR or FPLP Power Limited Cabl...

Page 10: ...m E O L resistor connected to the RS 485 positive and negative terminals 24V IN OUT S RS 485 IN OUT S R S 4 8 5 24V IN OUT S RS 485 IN OUT RAM 300LCD ADDRESS 1 RAM 300LCD ADDRESS 2 FA 300 FIRE ALARM P...

Page 11: ...5 3 Current Drain for Battery Calculations The maximum normal current drain will be during Lamp Test when all lamps are illuminated on one chassis at a time Thus the currents are Normal Standby 56 mA...

Page 12: ...ain for normal system operation Note Auxiliary relays will not operate when Fire Drill is operated Lamp Test Press the Lamp Test button momentarily to test all indicators except the CPU Fail LED All i...

Page 13: ...em a substitute for property owners renters or other occupants to act prudently to prevent or minimize the harmful effects of an emergency situation Building automation systems produced by the Mircom...

Page 14: ...ovide timely warning of fires caused by carelessness or safety hazards such as smoking in bed violent explosions escaping gas improper storage of flammable materials overloaded electrical circuits or...

Page 15: ...ication appliances such as sirens bells horns or strobes may not warn or waken a sleeping occupant if there is an intervening wall or door It is less likely that the occupants will be alerted or awake...

Page 16: ...5 Tel 905 660 4655 888 660 4655 Fax 905 660 4113 Mircom 2018 Printed in Canada Subject to changewithout priornotice www mircom com CANADA Main Office 25 Interchange Way Vaughan ON L4K 5W3 Tel 905 660...

Reviews: