![background image](http://html1.mh-extra.com/html/mircom/ra-1000-series/ra-1000-series_installation-and-wiring-manual_1805840008.webp)
DIP Switch Settings
4
DIP Switch Settings
Each annunciator assembly (main and adder chassis’) needs to be assigned a unique, sequential
Address via the Main Chassis DIP Switch SW1. DIP Switch SW2 is used to allow disabling of
some Front Panel push buttons (when individual switches are “ON” then the corresponding push
button is disabled)
.
The RA-1000 DIP switches are set as:
Checksum Select:
ON when used with FX-2000 (16 bit checksum)
OFF when used with FA-1000, FA-300 and FA-200 Series (8 bit checksum)
For FA-1000, FA-300, and FA-200 Series Panels
Set the annunciator “Address” (see the manual for the fire alarm control panel being used), as
follows in the table below:
DIP SWITCH SW1
DIP SWITCH SW2
SW1-1
= Address A0
SW2-1
= Disable System Reset button
SW1-2
= Address A1
SW2-2
= Disable Fire Drill button
SW1-3
= Address A2
SW2-3
= Disable Acknowledge button
SW1-4
= Address A3
SW2-4
= Disable General Alarm button
SW1-5
=
Must be set to “OFF” when
used with FA-1000, FA-300,
and FA-200 Series
SW2-5
=
Not Used
SW1-6
=
Not Used
SW2-6
=
Disable Auxiliary Disconnect
button
SW1-7
=
Not Used
SW2-7
=
Not Used
SW1-8
=
Checksum Select
SW2-8
=
Disable Signal Silence button
DIP
Switch
Positions
Annunciator Address
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
SW1-1 (A0)
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
SW1-2 (A1)
OFF
ON
ON
OFF
OFF
ON
ON
OFF
OFF
ON
ON
OFF
OFF
ON
ON
SW1-3 (A2)
OFF
OFF
OFF
ON
ON
ON
ON
OFF
OFF
OFF
OFF
ON
ON
ON
ON
SW1-4 (A3)
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
ON
ON
ON
ON
ON
ON
ON
Notes:
Annunciators on a common RS-485 connection must be numbered sequentially;
i.e.: 1,2,3,4, and not randomly such as 5,3,8, 14!! Note that NOT ALL annunciator
“Addresses” are valid for all Fire Alarm Control Panels. Refer to the Fire Alarm
Control Panel Manual for further information