Pre-installation inspections: 

1.  Verify that jumpers 

JP1

 and 

JP2 on the QDV-1000

 are over 

pins 2 and 3 for both

, that is the jumpers are in 

the 

left-most positions

 for both.  In case that the ‘Manual Message’ option is used, move JP2 over to pins 1 

and 2, which is the right-most position instead. 

2. Locate 

the 

J8 header

 on the QIF-5000B module; remove all jumper headers if any. 

3.  For a single stage system with voice recording to be played on the Evacuation channel 2, install the 

QDV-

0001 integrated circuit chip into socket U3 (this is the standard operation set up).

 

4.  For voice recording to be played on the Alert channel 3, install a QDV-0001 integrated circuit chip socket into 

U4. 

5.  For voice recording to be played on the Alert2 channel 4, install a QDV-0001 integrated circuit chip into socket 

U5.

 

J1

QDV-1000 DIGITIZED VOICE BOARD

PT1

PT2

PT3

PT4

PT5

JP1

J2

U4

U5

U6

U3

JP2

3  2  1

3  2  1

Evac.

Alert2 (Manual)

Alert

Background noise

Evac.  
Channel
2

Alert2
Channel
4

Alert
Channel 3

Header J1 connects to QDVP-100

TS1

TS1-2

TS1-1

MOVE JUMPER JP2 TO PINS 1 &2 IF ALERT 2
CHANNEL (MANUAL MESSAGE) IS USED.

Not Installed 
Not Used 

Paging 
Channel 1

LT-901 Rev.4 Aug 2006 

          Page 2 of 10 

Summary of Contents for QDV-1000

Page 1: ...p Beep Beep Channel 2 Message 1 For internal use only do not use 2 Temporal Tone Channel 2 Message 2 3 Boston Message Attention please the signal tone you have just heard indicated a report of an emer...

Page 2: ...ntegrated circuit chip into socket U3 this is the standard operation set up 4 For voice recording to be played on the Alert channel 3 install a QDV 0001 integrated circuit chip socket into U4 5 For vo...

Page 3: ...Windows Media Player or Windows Sound Recorder 2 The sound clip files to be recorded 3 Sound clip file SO 195 wav the 5 seconds of pre announcement tone LT 901 Rev 4 Aug 2006 Page 3 of 10 Procedure S...

Page 4: ...channel number and the new message number 4 Press the REC button on the QDVP 100 to start recording and play the message from the computer Press the STOP to end the recording 5 Play back the recorded...

Page 5: ...ed for alarm messages Special tone file SO 195 wav must be used 2 If Massachusetts Boston code signaling is used the evacuation tone SO 181 wav must be programmed in message position 2 of evacuation c...

Page 6: ...r 2 Locate the J8 header on the QIF 5000B Align the key on the ribbon cable header from QDV 1000 J2 with the opening of the J8 and plug the cable into the shrouded header 3 Connect a wire from termina...

Page 7: ...4 line with part1 repeat set at 255 and repeat all set at 255 o Message 1 cannot be used to build the play back message o For Mass Code operation see below 7 From the main system window under the Syst...

Page 8: ...re the QDV 1000 Channel 4 as show in the diagram below Also note that the Message of Part 2 is the message number of the Pre announce tone SO 195 wav recorded in Alert2 I C LT 901 Rev 4 Aug 2006 Page...

Page 9: ...d up do the following 1 Set the rotary switches on the QIF 5000B to 97 2 Move the jumper JP5 on the QIF 5000B to position 1 and 2 3 Press on the reset switch on the QIF 5000B 4 Wait for the green LED...

Page 10: ...onfiguration data to the QIF 5000B and wait until download completes 11 Once LED goes back to steady green may take 30 45 seconds replace jumper JP5 to position 2 and 3 During all the above operations...

Page 11: ......

Page 12: ...5 660 4113 Mircom 2011 Printed in Canada Subject to change without prior notice www mircom com U S A 4575 Witmer Industrial Estates Niagara Falls NY 14305 Tel 888 660 4655 905 660 4655 Fax 905 660 411...

Reviews: