FleX-Net
TM
Installation and Operation Manual
141
This screen capture shows input zone priority settings for the Mass Notification Node 2
FX-LOC(R) Active
As part of the Mass Notification requirements, an RAX-1048TZ Zone Annunciator is part of the MNS. Configure
one zone of the RAX-1048TZ per each FX-LOC(R) connected to the MNS (ACU). Each LED is configured to
illuminate when the respective FX-LOC(R) paging is in use.
Reset
As per UL, resets are handled separately for Fire/Central Control and the Mass Notification System. They are
mutually independent.
ACU Emergency Response Operation
1. Access control of ACU.
2. ACU will notify in use via LED on RAX-1048TZ/DS.
3. Select areas to receive paging or digitized messages or use all call.
4. Page or send digitized message as necessary.
Note:
The RAX-1048TZ/TZDS normally displays Initiating circuit status and trouble indication, the FleX-Net
TM
configuration must be used to configure each zone corresponding to a FX-LOC(R).