FleX-Net
TM
Installation and Operation Manual
127
Model QAA-5230S-70/25 Amplifier with 2 split 70V or 25V, 30 Watt Zones
• 70.7Vrms or 25V constant voltage output
• Each 30W output divided into 2 Class “B” 15W lines for split speaker line applications (two lines per zone with
staggered speakers); four fully supervised Class "B" speaker zones
• 30 watts per zone, 15 Watts per split
• Freq. response:
ULI bandwidth from 800 to 2800 Hz
• Harmonic Distortion less than 2.5% at 1 KHz
• Current Consumption:
standby:
55mA
alarm:
350mA, plus 65mA/Watt Speaker Power
Model QAA-5415-70 Amplifier with four 70V, 15 Watt Zones
• 70.7Vrms constant voltage output
• Four fully supervised Class "B" speaker zones, 15 watts per zone
• Freq. response:
ULI bandwidth from 800 to 2800 Hz
• Harmonic distortion less than 2.5% at 1 KHz
• Current consumption:
standby:
55mA
alarm:
350mA, plus 75mA/watt speaker power
Model QAA-5415-25 Amplifier with four 25V, 15 Watt Zones
• 25Vrms constant voltage output
• Four fully supervised Class "B" speaker zones
• 15 watts per zone
• Freq. response:
ULI bandwidth from 800 to 2800 Hz
• Harmonic distortion less than 2.5% at 1 KHz
• Current consumption:
standby:
55mA
alarm:
350mA, plus 75mA/watt speaker power
Model QMP-5101N or QMP-5101NV Paging Microphone
• Mounts in Mircom BB-1000, BB-5000, FX-LOC, and BBX-FXMNS (for QMP-5101NV) enclosures
• Current Consumption:
standby:
3mA
alarm:
7mA
Model QAZT-5302/DS Paging Selector Panel
• Mounts in Mircom BB-1000, BB-5000 and BBX-FXMNS enclosures
• Connects to QMP-5101N to provide 24 zones of paging control
• Up to one per QMP-5101N or QMP-5101NV
• Current Consumption:
standby:
10mA
alarm:
15mA
Model QMT-5302N or QMT-5302NV Master Telephone
• Mounts in Mircom BB-1000, BB-5000, FX-LOC, and BBX-FXMNS enclosures
• Current Consumption:
standby:
1mA
alarm:
13mA
Model QAZT-5302/DS Telephone Selector Panel
• Mounts in Mircom BB-1000, BB-5000, FX-LOC, and BBX-FXMNS enclosures
• Connects to QMT-5302N to provide 24 firefighters’ telephone zones
• Up to six selector panels per QMT-5302N
• Unlimited handsets allowed per telephone circuit, supports up to 5 handsets active at the same time
• Current Consumption:
standby:
10mA/5mA
alarm:
15mA/22mA