FleX-Net
TM
Installation and Operation Manual
101
Setup
QBB-5001/R Amplifier Installation
The following instructions are based on the assumption that the fire alarm is already installed.
1. Install the QBB-5001/R Audio Backbox and door in the desired location.
2. Install the QMB-5000B Motherboard / Card-Cage into the backbox.
3. Install the QBC-5000N Battery Charger into the backbox. Connect its cable to J1 on the motherboard.
4. Install the QPS-5000N Power Supply into the QBB-5001/R backbox. Be careful: the QPS-5000N is
very heavy
.
5. Connect the heavy orange - yellow - orange wires from the motherboard to the power supply being careful to
match the wire colour to the labelling on the power supply.
6. Connect the un-powered 120 VAC line power and chassis ground to the power supply following the labelling.
Ground the power supply to the box.
Do not apply AC power at this time.
7. Install the two 12 VDC batteries into the backbox.
8. Connect the battery cables from the motherboard to the batteries as shown in Figure 58, but do not connect
the cable between the batteries at this time.
When plugging in these amplifiers, the components are facing left. Slide the amplifier in place and to avoid damage,
making sure that the edge connector is properly mating with the header on the motherboard. Keep the amplifier as
straight and level as possible and use even pressure on the top and bottom. The amplifier is connected properly
after it snaps into place.
9. Connect and check (for opens, shorts, and ground) all the amplifiers' field wiring.
Before Turning the Power "ON"...
The entire system installation should be completed first.
To prevent sparking,
do not
connect the batteries. Connect the batteries after powering the system from the main
A.C. supply.
1. Check and secure all interconnection wiring cables.
2. Check and secure all interconnection wiring cables to the Fire Alarm Control Panel.
3. Check the A.C. power wiring for proper connection.
4. Check that the chassis is connected to earth ground.
Audio Configuration
The configuration of the FleX-Net
TM
is accomplished via the MSW-025 Personal Computer based Configurator
Software.
ATTENTION:
Powering the system with incorrectly installed amplifiers will cause permanent damage.
NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION, AND OTHER INVOLVED PARTIES
This product incorporates field-programmable software. In order for the product to comply with the requirements in
the Standard for Control Units and Accessories for Fire Alarm Systems, UL 864, certain programming features or
options must be limited to specific values or not used at all as indicated below.
Program feature or option
Permitted in UL 864? (Y/N)
Possible settings
Settings permitted in UL 864
Master Telephone Buzzer
Disable
No
Enabled or Disabled
Not permitted