background image

FA-102T Installation and Operation Manual

15

Warranty & Warning Information

Warning Please Read Carefully 

Note to End Users: This equipment is subject to terms and conditions of sale as follows:

Note to Installers 

This warning contains vital information. As the only individual in contact with system users, it is your 
responsibility to bring each item in this warning to the attention of the users of this system. Failure 
to properly inform system end-users of the circumstances in which the system might fail may result 
in over-reliance upon the system. As a result, it is imperative that you properly inform each 
customer for whom you install the system of the possible forms of failure. 

System Failures 

This system has been carefully designed to be as effective as possible. There are circumstances, 
such as fire or other types of emergencies where it may not provide protection. Alarm systems of 
any type may be compromised deliberately or may fail to operate as expected for a variety of 
reasons. Some reasons for system failure include: 

Inadequate Installation

A Fire Alarm system must be installed in accordance with all the applicable codes and standards in 
order to provide adequate protection. An inspection and approval of the initial installation, or, after 
any changes to the system, must be conducted by the Local Authority Having Jurisdiction. Such 
inspections ensure installation has been carried out properly.

Power Failure

Control units, smoke detectors and many other connected devices require an adequate power 
supply for proper operation. If the system or any device connected to the system operates from 
batteries, it is possible for the batteries to fail. Even if the batteries have not failed, they must be 
fully charged, in good condition and installed correctly. If a device operates only by AC power, any 
interruption, however brief, will render that device inoperative while it does not have power. Power 
interruptions of any length are often accompanied by voltage fluctuations which may damage 
electronic equipment such as a fire alarm system. After a power interruption has occurred, 
immediately conduct a complete system test to ensure that the system operates as intended.

Failure of Replaceable Batteries

 

Systems with wireless transmitters have been designed to provide several years of battery life 
under normal conditions. The expected battery life is a function of the device environment, usage 
and type. Ambient conditions such as high humidity, high or low temperatures, or large temperature 
fluctuations may reduce the expected battery life. While each transmitting device has a low battery 
monitor which identifies when the batteries need to be replaced, this monitor may fail to operate as 
expected. Regular testing and maintenance will keep the system in good operating condition.

•Compromise of Radio Frequency (Wireless) Devices

 

Signals may not reach the receiver under all circumstances which could include metal objects 
placed on or near the radio path or deliberate jamming or other inadvertent radio signal 
interference.

•System Users

 

A user may not be able to operate a panic or emergency switch possibly due to permanent or 
temporary physical disability, inability to reach the device in time, or unfamiliarity with the correct 
operation. It is important that all system users be trained in the correct operation of the alarm 
system and that they know how to respond when the system indicates an alarm.

Summary of Contents for FA-102T

Page 1: ...FA 102T Fire Alarm Control Panel LT 514 Rev 7 December 2009 Installation and Operation Manual Advanced Life Safety Solutions A C ON SIGNAL SILENCED 2 1...

Page 2: ......

Page 3: ...d Fault LED 3 Signal Trouble LED 3 Sequence of Operation 4 Normal 4 Alarm 4 Signal Silence 4 Reset Lamp Test 4 System Checkout 4 Power up and Troubleshooting 4 Wiring Tables and Information 8 Appendix...

Page 4: ...mounting details 5 Figure 2 Circuit Board Layout 6 Figure 3 Detection and signal wiring 7 Figure 4 Wiring table for detection zone 8 Figure 5 Wiring table for bells and horns 8 Figure 6 Alarm and tro...

Page 5: ...5 for dimensions Surface Mounting 1 Mark the location of the four mounting holes 2 Install the top two screws into the wall and place the panel over the screws 3 Install the bottom screws and tighten...

Page 6: ...ignal zone available for bells and horns providing 1 25A of signal power Refer to Figure 3 on page 7 for wiring instruction and to Figure 5 page 8 on for wire size Alarm and Trouble Relays Alarm and t...

Page 7: ...le LED will illuminate steadily and the buzzer will sound Buzzer Buzzer Silence Switch The buzzer will sound intermittently for any trouble For any alarm in the system the buzzer will sound steadily O...

Page 8: ...form a lamp test as well as reset the panel System Checkout Before turning the power on 1 Check all external wiring for opens shorts or grounds 2 Check that transformer cables are securely connected 3...

Page 9: ...5 Figure 1 Backbox and flush trim mounting details 13 3 4 12 3 4 1 11 16 Optional flush mounting trim model FA 102TR Four 7 32 dia 2 7 8 7 1 8 1 1 4 10 3 8...

Page 10: ...JW3 JW4 A C ON TRBL SIG SIL BATT GND TRANSFORMER P1 P2 P3 BATTERY P4 SIG 1 F1 2A BATTERY A C 2A F2 COM JW2 JW1 1 TB2 2 TRBL ALARM ZONE 1 TRBL ALARM ZONE 2 AUX TRBL ON DSW1 DIP SWITCHES 1 8 MD 733 DET...

Page 11: ...Heat Detector Bell F F S R Alarm threshold current is 21 mA Maximum loop resistance is 100 ohms ELR 3 9K 1 2W F S R TB2 Detection zone 1 F F ELR 3 9K 1 2W Signal zone Detection zone 2 22VDC 3mA STBY...

Page 12: ...5800 12 30400 9200 Note Maximum loop resistance should not exceed 100 ohms Total Signal Load Maximum Wiring Run to Last Device ELR Max Loop Resistance 18AWG 16AWG 14AWG 12AWG 0hms Amperes ft m ft m ft...

Page 13: ...Auxiliary common alarm relay contacts 28VDC 3A resistive Common trouble relay contacts 28VDC 3A resistive Cut JW3 for N O Cut JW4 for N C N O C N C TB2 TRL TRB A C ON 24V 24VDC 250 mA max 24VDC 50 mA...

Page 14: ...Mirtone PSD 7131 70 201000 003 1400 A 73471 PSD 7131 70 201000 005 2400 A 73494 PSD 7130 70 201000 001 1451 A B401B 73575 PSD 7130 70 201000 002 1451 A B406B 73495 73486 PSD 7130 70 201000 003 2451 A...

Page 15: ...FA 102T Installation and Operation Manual 11 Underwriters Laboratories of Canada ULC Canadian Signal Zone Compatible Devices Make Model Mircom BL 6B...

Page 16: ...Appendix A Compatible Devices 12 Page Intentionally Left Blank...

Page 17: ...FA 102T Installation and Operation Manual 13 Page Intentionally Left Blank...

Page 18: ...ce with Canadian Electrical Code C22 1 Part 1 Section 32 IMPORTANT NOTICE The main AC branch circuit connection for the Fire Alarm Control Unit must provide a dedicated continuous power without provis...

Page 19: ...om batteries it is possible for the batteries to fail Even if the batteries have not failed they must be fully charged in good condition and installed correctly If a device operates only by AC power a...

Page 20: ...cape in time to avoid injury or death Alarm Notification Appliances Alarm Notification Appliances such as sirens bells horns or strobes may not warn people or waken someone sleeping if there is an int...

Page 21: ...e exception that Mircom shall not be responsible for any customs fees taxes or VAT that may be due Conditions to Void Warranty This warranty applies only to defects in parts and workmanship relating t...

Page 22: ...may be revised from time to time will be charged for each unit repaired Products which Mircom determines not to be repairable will be replaced by the nearest equivalent product available at that time...

Page 23: ......

Page 24: ...han ON L4K 5W3 Tel 905 660 4655 Fax 905 660 4113 Mircom 2009 Printed in Canada Subject to change without prior notice www mircom com U S A 4575 Witmer Industrial Estates Niagara Falls NY 14305 Tel 1 8...

Reviews: