FA-102T Installation and Operation Manual
9
Figure 6: Alarm and trouble relay contacts and remote annunciation
wiring instructions
Auxiliary common
alarm relay contacts
28VDC, 3A (resistive)
Common trouble relay
contacts 28VDC, 3A
(resistive)
Cut JW3 for N.O.
Cut JW4 for N.C.
N.O.
C
N.C.
TB2
TRL
TRB
A.C. ON
24V+
24VDC, 250 mA max.
24VDC, 50 mA max.
unsupervised
unsupervised
24VDC, 50 mA max.
1.5K
1.5K
1.5K
remote trouble
LED (amber)
buzzer
LED (green)
remote trouble
remote AC ON