background image

Sequence of Operation

4

Sequence of Operation

Refer to Figure 2 on page 6 for the location of indicators and controls.

Normal

All indicators are normally OFF except for the green

 

A.C. On LED.

Alarm

A red zone alarm LED will illuminate steadily for an incoming alarm.

Signal Silence

If the 60 second signal silence inhibit is selected, the signal cannot be silenced for 60 seconds after 
an alarm initiation. Once the 60 seconds have expired, pushing the signal silence switch to the right 
will silence all the bells and horns. Once the signal has been silenced, the signal silenced

 

LED will 

illuminate. If the switch is in the OFF normal position to the right while there is no alarm condition, 
the panel will indicate trouble.

Reset/Lamp Test

Operating the reset switch will restore all latched functions in the panel. The smoke detectors will 
reset if all products of combustion are cleared from their chambers. Holding the reset switch for five 
seconds will cause the panel to preform a lamp test as well as reset the panel.

System Checkout

Before turning the power on,

1. Check all external wiring for opens, shorts or grounds.
2. Check that transformer cables are securely connected.
3. Check the 

A.C.

 power wiring for proper connection. To prevent sparking, 

do not

 connect 

batteries.

4. Check that all switches are in the normal position to the left.

Power up and Troubleshooting

1. After completing all of the system checkout procedures, power up the panel. The A.C. On LED 

should illuminate.The trouble buzzer should sound intermittently, the Common Trouble LED 
should flash, indicating battery fault.

2. Connect the batteries carefully, observing the correct polarity.The Common Trouble LED

 

should extinguish. If the Common Trouble LED stays on, check the front panel for the 
illumination of the following LEDs:

Battery LED 

indicates that the battery voltage may be too low (below 20.4V). Replace 

batteries as required.

Ground Fault LED

 indicates a ground on one or more of the extended wires.

Zone Trouble LED

 indicates an open loop or a signal

 

silence switch is in the OFF normal 

position to the right.

Signal Trouble LED

 indicates an open loop or short in the signal zone.

Summary of Contents for FA-102T

Page 1: ...FA 102T Fire Alarm Control Panel LT 514 Rev 7 December 2009 Installation and Operation Manual Advanced Life Safety Solutions A C ON SIGNAL SILENCED 2 1...

Page 2: ......

Page 3: ...d Fault LED 3 Signal Trouble LED 3 Sequence of Operation 4 Normal 4 Alarm 4 Signal Silence 4 Reset Lamp Test 4 System Checkout 4 Power up and Troubleshooting 4 Wiring Tables and Information 8 Appendix...

Page 4: ...mounting details 5 Figure 2 Circuit Board Layout 6 Figure 3 Detection and signal wiring 7 Figure 4 Wiring table for detection zone 8 Figure 5 Wiring table for bells and horns 8 Figure 6 Alarm and tro...

Page 5: ...5 for dimensions Surface Mounting 1 Mark the location of the four mounting holes 2 Install the top two screws into the wall and place the panel over the screws 3 Install the bottom screws and tighten...

Page 6: ...ignal zone available for bells and horns providing 1 25A of signal power Refer to Figure 3 on page 7 for wiring instruction and to Figure 5 page 8 on for wire size Alarm and Trouble Relays Alarm and t...

Page 7: ...le LED will illuminate steadily and the buzzer will sound Buzzer Buzzer Silence Switch The buzzer will sound intermittently for any trouble For any alarm in the system the buzzer will sound steadily O...

Page 8: ...form a lamp test as well as reset the panel System Checkout Before turning the power on 1 Check all external wiring for opens shorts or grounds 2 Check that transformer cables are securely connected 3...

Page 9: ...5 Figure 1 Backbox and flush trim mounting details 13 3 4 12 3 4 1 11 16 Optional flush mounting trim model FA 102TR Four 7 32 dia 2 7 8 7 1 8 1 1 4 10 3 8...

Page 10: ...JW3 JW4 A C ON TRBL SIG SIL BATT GND TRANSFORMER P1 P2 P3 BATTERY P4 SIG 1 F1 2A BATTERY A C 2A F2 COM JW2 JW1 1 TB2 2 TRBL ALARM ZONE 1 TRBL ALARM ZONE 2 AUX TRBL ON DSW1 DIP SWITCHES 1 8 MD 733 DET...

Page 11: ...Heat Detector Bell F F S R Alarm threshold current is 21 mA Maximum loop resistance is 100 ohms ELR 3 9K 1 2W F S R TB2 Detection zone 1 F F ELR 3 9K 1 2W Signal zone Detection zone 2 22VDC 3mA STBY...

Page 12: ...5800 12 30400 9200 Note Maximum loop resistance should not exceed 100 ohms Total Signal Load Maximum Wiring Run to Last Device ELR Max Loop Resistance 18AWG 16AWG 14AWG 12AWG 0hms Amperes ft m ft m ft...

Page 13: ...Auxiliary common alarm relay contacts 28VDC 3A resistive Common trouble relay contacts 28VDC 3A resistive Cut JW3 for N O Cut JW4 for N C N O C N C TB2 TRL TRB A C ON 24V 24VDC 250 mA max 24VDC 50 mA...

Page 14: ...Mirtone PSD 7131 70 201000 003 1400 A 73471 PSD 7131 70 201000 005 2400 A 73494 PSD 7130 70 201000 001 1451 A B401B 73575 PSD 7130 70 201000 002 1451 A B406B 73495 73486 PSD 7130 70 201000 003 2451 A...

Page 15: ...FA 102T Installation and Operation Manual 11 Underwriters Laboratories of Canada ULC Canadian Signal Zone Compatible Devices Make Model Mircom BL 6B...

Page 16: ...Appendix A Compatible Devices 12 Page Intentionally Left Blank...

Page 17: ...FA 102T Installation and Operation Manual 13 Page Intentionally Left Blank...

Page 18: ...ce with Canadian Electrical Code C22 1 Part 1 Section 32 IMPORTANT NOTICE The main AC branch circuit connection for the Fire Alarm Control Unit must provide a dedicated continuous power without provis...

Page 19: ...om batteries it is possible for the batteries to fail Even if the batteries have not failed they must be fully charged in good condition and installed correctly If a device operates only by AC power a...

Page 20: ...cape in time to avoid injury or death Alarm Notification Appliances Alarm Notification Appliances such as sirens bells horns or strobes may not warn people or waken someone sleeping if there is an int...

Page 21: ...e exception that Mircom shall not be responsible for any customs fees taxes or VAT that may be due Conditions to Void Warranty This warranty applies only to defects in parts and workmanship relating t...

Page 22: ...may be revised from time to time will be charged for each unit repaired Products which Mircom determines not to be repairable will be replaced by the nearest equivalent product available at that time...

Page 23: ......

Page 24: ...han ON L4K 5W3 Tel 905 660 4655 Fax 905 660 4113 Mircom 2009 Printed in Canada Subject to change without prior notice www mircom com U S A 4575 Witmer Industrial Estates Niagara Falls NY 14305 Tel 1 8...

Reviews: