background image

Page 10

REPORTING FORMATS

For Central Station reports, the events are recorded as explained in the tables below. 

ADEMCO CONTACT-ID

DACT-100A Internal Events:

Event Description

Event Family

Qualifier

Code

Group #

Contact #

Phone Line #1 trouble detected

Trouble

New event

1 351

00

000

Phone Line #2 trouble detected

Trouble

New event

1 352

00

000

Phone Line #1 trouble restored

Trouble

Restore

3 351

00

000

Phone Line #2 trouble restored

Trouble

Restore

3 352

00

000

Failure to report to an Account

Trouble

New event

1 354

Acct #

Acct #

Report to an Account successful

Trouble

Restore

3 354

Acct #

Acct #

Periodic (24 hr) Test Event (Normal)

Test

New event

1 602

00

000

Periodic (24 hr) Test Event (Off Normal)

Test

New event

1 608

00

000

Manually initiated dialer test

Test

New event

1 601

00

000

DACT-100A External Events:

Event Description

Event Family

Qualifier

Code

Group #

Contact #

Fire Alarm 

Alarm

New event

1 110

00

000

Fire Alarm restored

Alarm

Restore

3 110

00

000

System Trouble detected

Trouble

New event

1 300

00

000

System Trouble restored

Trouble

Restore

3 300

00

000

Supervisory condition

Supervisory

New event

1 200

00

000

Supervisory restored

Supervisory

Restore

3 200

00

000

SECURITY INDUSTRIES ASSOC. SIA-DCS

DACT-100A Internal Events :

Event Description

Event Family

Qualifier

SIA Event Code

Parameter

Phone Line #1 trouble detected

Trouble

New event

LT

00

Phone Line #2 trouble detected

Trouble

New event

LT

00

Phone Line #1 trouble restored

Trouble

Restore

LR

00

Phone Line #2 trouble restored

Trouble

Restore

LR

00

Failure to report to an Account

Trouble

New event

RT

Acct #

Report to an Account successful

Trouble

Restore

YK

Acct #

Periodic (24 hr) Test Event (Normal)

Test

New event

RP

00

Periodic (24 hr) Test Event (Off Normal)

Test

New event

RY

00

Manually initiated dialer test

Test

New event

RX

00

DACT-100A External Events:

Event Description

Event Family

Qualifier

SIA Event Code

Parameter 

Fire Alarm 

Alarm

New event

FA

00

Fire Alarm restored

Alarm

Restore

FH

00

System Trouble detected

Trouble

New event

FT

00

System Trouble restored

Trouble

Restore

FJ

00

Supervisory condition

Supervisory

New event

FS

00

Supervisory restored

Supervisory

Restore

FR

00

Summary of Contents for DACT-100A

Page 1: ...pecifications contained in this manual are subject to change without prior notice by the manufacturer DACT 100A Digital Communicator INSTALLATION and OPERATION MANUAL 2005 by Mircom Technologies Limit...

Page 2: ...n the U S A Page 2 CONNECTIONS AND SETTINGS Page 3 FIELD WIRING Page 4 POWER UP PROCEDURES Page 5 SYSTEM CONFIGURATION OPERATION Page 7 REPORTING FORMATS Page 9 COMPATIBLE FIRE ALARM CONTROL PANELS Pa...

Page 3: ...ols T The DACT 100A can transmit Common Alarm Common Supervisory and Common Trouble information on two telephone lines The DACT Products continuously supervise the state of each of two connected Telco...

Page 4: ...d Fire Alarm Control Panel under Standard 864 Control Units for Fire Protective Signalling Systems These Communicators complywith the National Fire Protection Association NFPA performance requirements...

Page 5: ...m Control Panel FACP P2 RS 485 Connection for future expansion P4 Connector for CFG 100 Configuration Module I2 Status Indicator LED for Telco Line 1 Red when the line is in use Amber when there is a...

Page 6: ...one on the first Telephone Line via the required RJ31X Connector Line 2 Input Tip Ring To the second Telephone Line via the required RJ31X Connector Line 3 Output Tip Ring To an optional Premise Telep...

Page 7: ...de 2222222 for installer Enter 2 digit ITEM number to configure To scroll down list of items press or to scroll up 8 When you try to enter a 2 digit number the following screen will appear Please ente...

Page 8: ...Contact ID Format is _ Format is _ Press when done Press when done or to cancel or to cancel 13 Enter 11 to initiate the test report the screen will go through the following sequences Digital Communic...

Page 9: ...ator Reporting event Date Time The next screen is Digital Communicator Waiting for KISS Date Time If the screen stays in the Waiting for KISS mode then you should contact our Tech Support otherwise wh...

Page 10: ...associated with individual level I OPERATOR and II INSTALLER 10 I II Event Logging Flush all events Terminate any in progress event reporting Remove report pending trigger i e cancel attempts to repor...

Page 11: ...nt 1 Choose which Account 1 or 2 will be the first to be attempted to be reached by the DACT when a TROUBLE event is to be reported See ITEM 50 for a description of the DACT report attempt operation 5...

Page 12: ...Trouble New event 1 300 00 000 System Trouble restored Trouble Restore 3 300 00 000 Supervisory condition Supervisory New event 1 200 00 000 Supervisory restored Supervisory Restore 3 200 00 000 SECUR...

Page 13: ...roved SIA DCS and Ademco Contact ID Radionics Model D6500 Receiver ULI Approved Ademco Contact ID Radionics Model D6600 Receiver ULI Approved SIA DCS and Ademco Contact ID All Circuits are Power Limit...

Page 14: ...If a device operates only by AC power any interruption however brief will render that device inoperative while it does not have power Power interruptions of any length are often accompanied by voltage...

Page 15: ...appliances may be interfered with by other noise sources such as stereos radios televisions air conditioners or other appliances or passing traffic Audible notification appliances however loud may not...

Page 16: ...llation environment for the products damage caused by use of the products for purposes other than those for which it was designed damage from improper maintenance damage arising out of any other abuse...

Page 17: ...ged for each replacement unit WARNING Mircom Technologies Ltd recommends that the entire system be completely tested on a regular basis However despite frequent testing and due to but not limited to c...

Page 18: ...area code ____________________ Reporting Format 9 Contact ID 9 SIA _________________________________________________________________________________________ Account 2 Identification max 6 digits _ _...

Page 19: ......

Page 20: ...Tel 905 660 4655 Fax 905 660 4113 Mircom 2006 Printed in Canada Subject to change without prior notice www mircom com Advanced Life Safety Solutions U S A 60 Industrial Parkway PMB 278 Cheektowaga NY...