Page 1
INTRODUCTIONS AND FEATURES
DACT-100A:
A single board Digital Communicator that can connect via Contact Closure Inputs on a single ribbon cable to a
Mircom Fire Alarm Control Panel (FACP) such as the FA-200 Series. It can transmit Common Alarm, Common
Supervisory, and Common Trouble information on two telephone lines.
T
Communicates to a FACP via
Contact Closure Inputs
(DACT-100A).
T
User Configurable with
CFG-100 Configuration Tool
. This includes a 4-Line LCD Display and Keypad in a rugged metal
enclosure, with a ribbon cable to connect to the Communicator.
T
Communicates to a
Central Monitoring Station
using
Ademco Contact ID
or
SIA DCS
Protocols.
T
The
DACT-100A
can transmit Common Alarm, Common Supervisory and Common Trouble information on two telephone
lines.
The
DACT Products
continuously supervise the state of each of two connected Telco Lines (at approximately 1
minute intervals) by a Line-DC level measurement. If supervision fails, a Line #1 or Line #2 Trouble event will be
reported. Once a Line has been restored, a Line Trouble Restored event will be reported. The product will
always
report events sorted in the order in which they are received / recognized. The products are capable of reporting
multiple event to a single Account number, within a single call session. Up to 3 retries, for a single message not yet
reported, will be made within a single call-attempt. A failure to communicate to either or both Accounts will generate
a corresponding event which will be queued for reporting.
Summary of Contents for DACT-100A