background image

9

Plumbing (checklist in detail)

1.

  The appliance is designed to operate with a minimum maintained inlet pressure 

of 70 kPa (0.7 bar), 100 kPa (1.0 bar) recommended, up to a maximum static 

inlet pressure of 1000 kPa (10 bar).

2.

  When installed in very hard water areas (above 200 ppm temporary hardness) 

your installer may advise the installation of a water treatment device, to reduce 

the effects of limescale formation. Your local water company will be able to 

advise the hardness of water in your area.

3.

  It is recommended that a non-restrictive (free flowing) isolating valve is fitted 

as part of the cold water supply pipe to allow the complete maintenance of the 

Mira Sport Thermostatic. 

Do not

 use a valve with a loose washer plate (jumper) 

as this can lead to a build up of static pressures.

4.

  The appliance is suitable only for installation within the shower area. It is fitted 

with a pressure relief device and must be positioned over a water catchment 

area with the controls at a convenient height for all users.

5.

  The appliance must be fitted onto a finished flat and even wall surface (this 

wall surface should be tiled or waterproofed). 

Do not

 fit the appliance to the 

wall and tile up to the case. For safety requirements, an air gap must be left 

behind the appliance.

6.

  Avoid layouts where the shower hose will be sharply kinked. This may reduce 

the life of the hose.

7.

  A Soap Dish/Hose Retaining Ring is supplied to prevent the handset from 

dropping below the spill-over level of the bath or shower, which could lead to 

contamination from back-siphoning. The supplied Hose Retaining Ring should 

meet the great majority of user requirements for shower installations with 

flexible outlet fittings. However, there will be occasions when it will not provide 

a suitable solution. In these instances an outlet double checkvalve, e.g. a Mira 

DCV-H, must be fitted. This will increase the required supply pressure typically 

by 10 kPa (0.1 bar) refer to section: 

'Accessories'

.

8.

  Supply  pipework  must  be  flushed  to  clear  debris  before  connecting  to  the 

appliance.

9.

  To avoid damage to the case when soldered fittings are used, pre-solder the 

pipework and fittings before connecting them to the inlet connector assembly. 

Refrain from applying excessive force when making any connections. Always 

provide mechanical support when making the plumbing connections.

10.

  The appliance is fitted with a brass inlet compression assembly for connecting 

to a 15 mm supply pipe from the top, bottom or back. Double checkvalves, 

fitted in the inlet supply to the appliance, cause a pressure build-up, which 

could exceed the maximum static inlet pressure and damage the appliance.

Summary of Contents for Sport Thermostatic 9.0

Page 1: ...1 Installation User Guide These instructions are to be left with the user 9 0 9 8 K W MIRA SPORT THERMOSTATIC ELECTRIC SHOWER...

Page 2: ...ation 12 Commissioning 14 User Instructions 16 Thermostatic Control 17 Fault Diagnosis 20 Maintenance 24 Inlet Filter Cleaning Renewing 24 Dimensions 25 Spare Parts 26 Accessories 28 Wiring Diagram 29...

Page 3: ...h Mira Sport Thermostatic 9 8 A 9 8 kW 240 V AC 9 0 kW 230 V AC heater Available in white chrome finish Recommended Usage Domestic Light Commercial Heavy Commercial Healthcare Guarantee For domestic i...

Page 4: ...ust be local to the appliance and may be a ceiling mounted pullcord type or a wall mounted switch fitted in an appropriate zone area 7 In accordance with BS7671 a 30mA Residual Current Device RCD must...

Page 5: ...dren should be supervised to ensure that they do not play with the shower 20 Always switch off the shower at the electrical isolating switch when not in use 21 The showerhead must be de scaled regular...

Page 6: ...rt names and to confirm that the parts are included q 1 x Olive Documentation q 1 x Customer Support Brochure q 1 x Installation Template q 1 x Installer Checklist q 1 x Compression Nut q 3 x Fixing S...

Page 7: ...cal 2 1 The Mira Sport Thermostatic 9 0 kW 240 VAC 8 2 kW 230 VAC requires a 40 Amp circuit protection device The Mira Sport Thermostatic 9 8 kW 240 VAC 9 0 kW 230 VAC requires a 45 Amp circuit protec...

Page 8: ...chment area 5 Fitted to finished wall surface 6 No sharp hose kinks 7 Fittings should be positioned with a greater than 25 mm gap If this is not achievable then a outlet double checkvalve must be fitt...

Page 9: ...an air gap must be left behind the appliance 6 Avoid layouts where the shower hose will be sharply kinked This may reduce the life of the hose 7 A Soap Dish Hose Retaining Ring is supplied to prevent...

Page 10: ...2 Shower unit is earthed 3 The minimum required supply cable size must conform to BS 7671 4 Double pole isolating switch 5 Do not twist live or neutral cable cores 6 Electrical connections are tightl...

Page 11: ...size of 4 0 mm if the cable is not mechanically protected 2 5 mm if mechanically protected 3 Supply cable see opposite 4 As a guide only and in accordance with BS 7671 we recommend close circuit prote...

Page 12: ...Mira Sport Attention Installer Caution Do not drill into buried cables or pipes Drill and plug the three holes using template Remove Cover and determine supply pipe position For back inlet use solder...

Page 13: ...wires are clear of all mounting holes Refit the Service Tunnel and Cover Make sure they fit correctly Do not overtighten screws Do not use alternative screws to secure the Cover This can cause intern...

Page 14: ...structions section before continuing COMMISSIONING Electrical supply is turned off at the mains Turn control to full cold Turn water supply fully on Check for water leaks Set control to LOW Switch on...

Page 15: ...Set control to HIGH _ The temperature will rise further Adjust temperature as required Flow rate will adjust automatically Press STOP button light on the button goes out Shower flow will continue for...

Page 16: ...r the lower the flow rate and vice versa _ _ _ Heated water is produced by adjusting the flow of cold water passed through a heater tank The shower has three heater settings How Your Electric Shower W...

Page 17: ...mperature across the range from hot to cold whilst also dealing with fluctuations in electrical and water supplies As a result there is a temperature limit the shower cannot go beyond For safety this...

Page 18: ...ired operating parameters refer to section Specifications _ For a cold shower select LOW For a summer warm shower select MEDIUM For a winter warm shower select HIGH During extremes of mains water supp...

Page 19: ...ew seconds before stopping Isolate power _ Switch on electrical supply Press START button Light on the button comes on Set to desired position Allow 10 15 seconds for any temperature adjustments to re...

Page 20: ...g possible electrical fault Switch on electrical s up p l y vi a the pullcord or wall mounted switch Renew the fuse or reset the MCB R C D I f f a u l t persists contact your installer S h o w e r cyc...

Page 21: ...icient water supply pressure for shut off Inlet valve faulty The minimum static pressure to ensure shut off and prevent dripping is 20 kPa 0 2 bar N o t e I f o t h e r appliances are operating static...

Page 22: ...r appliances whilst shower is in use Remove and clean Check case inserts are cut and fitted correctly Make sure electrical and plumbing services are not interfering with location Replace Replace Cons...

Page 23: ...will not turn off On On Off On Any Any InletValve Solenoid or Start Stop switch faulty Supply pressure below 20 kPa 0 2 bar R e p l a c e a s necessary Contact local water company Check mains water s...

Page 24: ...ross the flats of the metal connector Unscrew the filter using another wrench as shown Clean or renew the Filter as necessary Refit in reverse order making sure the Filter is screwed fully home Do not...

Page 25: ...25 DIMENSIONS 205 mm 85 mm 369 mm...

Page 26: ...240 V AC 1563 533 Thermostatic Valve Heater Tank 9 8 kW 240 V AC 1563 534 Outlet Connector Assembly 1563 536 Temperature Control Belt Thermostatic 1563 538 Temperature Cam Pulley 1563 540 Inlet Valve...

Page 27: ...switches A minimum air gap of 4 mm must be maintained between the connectors after assembly 405 58 406 27 416 38 1563 719 416 48 416 51 872 01 872 28 1563 532 1563 533 1563 538 1563 509 1563 543 A A...

Page 28: ...o a solid wall Everclear Showerhead White 2 1616 030 Chrome 2 1616 031 Mira s new Everclear range has been specially designed for hard water areas and reduces the risk of lime scale build up Logic Sho...

Page 29: ...ROWN BROWN BROWN BROWN RED RED RED GREEN GREEN BLUE Thermal Cutout Dual Disc L Solenoid Valve Pressure Power Selector Switch Low Flow Neon Start Stop Neon N Tank Connection Inlet Connector Internal Wi...

Page 30: ...30 NOTES...

Page 31: ...31 NOTES...

Page 32: ...e for a Service Technician to call If the performance of your product declines check in this manual to see if simple home maintenance is required If you require further assistance call our Customer Se...

Reviews: