ReVeRseD InLeT suPPLIes
the Mira Element thermostatic Mixer is supplied with inlet connections
Hot - Left,
Cold - Right
as standard. if the hot and cold water supply pipes have been reversed
during installation the thermostatic cartridge must be removed and rotated 180°.
1.
isolate the hot and cold water supplies.
2.
Unscrew and remove the control lever handle.
3.
loosen the Grubscrew (by approximately 4 turns) and pull off the control lever
and Bearing.
4. Built-in Models only:
4.1
carefully unclip the concealing Plate from the Backplate.
note!
Use a screwdriver in the cutout to assist separation.
4.2
Unscrew the two shroud screws and remove the Backplate from the
Mixer.
5.
Fit the ‘o’ Key (supplied) onto the cartridge nut and turn anticlockwise. Unscrew
fully and pull the cartridge from the Mixer Body.
6.
rotate the cartridge 180°.
7.
Make sure that the two Cartridge Inlet Seals are fitted and carefully push into
the Body, aligning the cartridge lugs into the Body slots.
note!
check that the cartridge lug stamped ‘h’ is aligned with the hot inlet
supply.
Important!
Take care when fitting the Cartridge as damage to the Cartridge
inlet seals may result in dripping from the shower head.
8.
tighten the nut by turning the ‘o’ Key clockwise.
9. Built-in Models only:
refer to section:
‘Control Assembly (Built-in Models)’
and follow instructions 4 to 9.
10.
With the lug in the 8 o’clock position fit the Bearing into the Concealing Plate
(refer to illustration).
11.
Make sure that the Hub is positioned fully clockwise and refit the Control Lever
with the Grubscrew at the bottom, retighten the Grubscrew and refit the Control
lever handle.
12.
Before using the shower, refer to section:
‘Commissioning’
.